| Plan Review Notes For Permit 19090553 |
| Permit Number |
19090553 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2019-12-12 14:53:45 | PLUMBING COMMENTS: APPROVED W/PROVISO | | | SEE PLAN SHEET 4 | | | A. PROVIDE ACCESSIBLE SHUT OFF VALVES FOR THE TUB PER | | | FBC PL 606.2 AND 606.3 | | | B. REPLACE EXISTING WATER HEATER WITH NEW; SEE ATTACHED | | | SUBMITTAL | | | C. PROVIDE VACUUM BREAKER FOR HAND HELD SHOWER; | | | D. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE | | | AS DEFERRED SUBMITTALS THE FOLLOWING ITEMS INCLUDED | | | WITH THE K-156-LCP BELAY WALK IN TUB: 1) N/A; 2) K-368 | | | HAND SHOWER HOLDER; 3) K-438-K BATH VALVE WITH | | | DIVERTER. THE DOCUMENTS SHALL BE SUBMITTED, APPROVED | | | AND ON SITE PRIOR TO FINAL INSPECTION. PROCEED AT YOUR | | | OWN RISK. | | | E. PROVIDE EXPANSION TANK AT WATER HEATER | | | | | 2019-12-12 14:37:22 | PLUMBING COMMENTS: APPROVED W/PROVISO | | | SEE PLAN SHEET 4 | | | 1. PROVIDE ACCESSIBLE SHUT OFF VALVES FOR THE TUB PER | | | FBC PL 606.2 AND 606.3 | | | 2. REPLACE EXISTING WATER HEATER WITH NEW; SEE ATTACHED | | | SUBMITTAL | | | 3. PROVIDE VACUUM BREAKER FOR HAND HELD SHOWER; | | | 4. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE | | | AS DEFERRED SUBMITTALS THE FOLLOWING ITEMS INCLUDED | | | WITH THE K-156-LCP BELAY WALK IN TUB: 1) MANUFACTURER?S | | | SPEC FOR THE KOHLER 1283230 THERMOSTATIC MIXING VALVE | | | (FBC PL 424.5); 2) K-368 HAND SHOWER HOLDER; 3) K-438-K | | | BATH VALVE WITH DIVERTER. THE DOCUMENTS SHALL BE | | | SUBMITTED, APPROVED AND ON SITE PRIOR TO FINAL | | | INSPECTION. PROCEED AT YOUR OWN RISK. | | | |
|