| 2019-11-14 13:11:24 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | NFPA 99 = HEALTH CARE FACILITIES CODE |
| | NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | PLEASE NOTE THAT I HAVE TRIED TO REACH OUT TO THE |
| | BUILDER AND THE PLUMBER FOR CLARIFICATIONS AND HAVE NOT |
| | BEEN ABLE TO GET RESPONSE. |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | PLEASE NOTE THAT I HAVE TRIED TO REACH OUT TO THE |
| | BUILDER AND THE PLUMBER FOR CLARIFICATIONS AND HAVE NOT |
| | BEEN ABLE TO GET RESPONSE. |
| | |
| | 1. SECOND REQUEST; PER WPB FBC 107.2.1, PROVIDE |
| | MANUFACTURER SPECIFICATION FOR TUB VALVE. ADDITIONALLY, |
| | PLEASE PROVIDE THE MANUFACTURER?S TECHNICAL |
| | SPECIFICATION/CUT SHEETS WITH MODEL NUMBER SELECTED |
| | (THERE ARE TWO SEPARATE MODEL NUMBERS LISTED ON TWO |
| | SEPARATE PAGES), SHOWING ALL TRIM, ROUGH-IN, INTERNAL |
| | PIPING, TRIM, ELECTRICAL CHARACTERISTICS, PUMP, |
| | MECHANICAL BOOSTER HEATER, AND ACCESS PANEL; IN-LINE |
| | HEATER AS WELL AS OTHER PERTINENT OPTIONS NOTED ON THE |
| | FAIRBANKS CUSTOMER INFORMATION SHEET. INCLUDE VACUUM |
| | BREAKER FOR HAND HELD SHOWER (FBC PL 424.2). |
| | 2. PER WPB FBC 107.2.1, DESIGNATE ONE OF THE PLAN |
| | SHEETS SUBMITTED AS A PLUMBING INFORMATION PLAN. NOTE |
| | ON THE PLAN ACCESSIBLE SEPARATE SHUT OFF VALVES FOR THE |
| | TUB (FBC PL 606.2 AND 606.3). |
| | 3. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER |
| | SPECIFICATION FOR NEW WATER HEATER AND VERIFY THAT THIS |
| | IS A REPLACEMENT OF THE EXISTING WATER HEATER WITH THE |
| | SAME FOOTPRINT AS THE ORIGINAL. NOTE TO REFLECT THAT ON |
| | THE PLAN SHEET SUBMITTED AS A PLUMBING INFORMATION |
| | PLAN. |
| | 4. THE SUBMITTAL FOR THE REQUIRED TEMPERATURE LIMITING |
| | DEVICE (FBC PL 424.5) IS SOMEWHAT ILLEGIBLE AND IS |
| | CONVOLUTED. PER WPB FBC 107.2.1, PROVIDE CLEAN AND |
| | LEGIBLE CUT SHEET(S). |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | |