| Plan Review Notes For Permit 19090553 |
| Permit Number |
19090553 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-10-02 10:34:25 | 1ST REVIEW: 19090553 | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. PROVIDE MANUFACTURE SPECIFICATIONS FOR TUB VALVE. | | | PER WPB AMEND TO FBC 107.2.1 SHALL COMPLY WITH NSF 372 | | | + 61 | | | 2. SHUT OFF VALVES FOR THE TUB SHALL REMAIN ACCESSIBLE. | | | PER FBC PL 606.2, 606.3 | | | 3. A WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO | | | ASSE 1070 OR CSA B125.3,IS REQUIRED ON THE TUB VALVE. | | | PER FBC PL 424.5 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] |
|