| Plan Review Notes For Permit 19090551 |
| Permit Number |
19090551 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-12-19 15:35:44 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FIRST COMMENT WAS NOT ADDRESSED. THE GENERATOR PAD | | | DETAILS THAT WERE SUBMITTED DO NOT HAVE THE ENGINEER'S | | | ORIGINAL SIGNATURE AS REQUIRED BY SECTION 471.025, | | | F.S., AND RULE 61G15-23.001, F.A.C. SUBMIT TWO SETS OF | | | GENERATOR PAD AND GENERATOR TO PAD ANCHORING DETAILS. | | | PRE-FABRICATED PADS REQUIRE SIGNED AND SEALED | | | ENGINEERING. FBC 107.2.1 |
|