2019-09-24 11:43:57THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE INDICATIONS OF 45.5 PAINTING FIRE
 SUPPRESSION PIPING.
  
 ANY WORK ON THE ANY FIRE SPRINKLER EQUIPMENT SHALL BE
 COORDINATED WITH THE FIRE SPRINKLER CONTRACTOR.
  
 ALL FIRE SPRINKLER HEADS SHALL BE PROTECTED FROM ANY
 PAINITNG MATERIAL.
  
 ANY PAINTED FIRE SPRINKJLER HEADS SHALL BE REPLACED
 THROUGH SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE AN
 APPLICABLE CONSTRUCTION NOTE OF THE RESUBMITTAL.
  
  
  
 2) THERE ARE INDICATIONS OF 25.3 MECHAICAL PIPE AND
 HANGERS.
  
 ANY WORK ON PIPE AND HANGERS INVOLVING THE FIRE
 SPRINKLER SYSTEM SHALL BE DONE UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS BY CERTIFIED FIRE SPRINKLER
 CONTRACTORS.
  
 PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE AN
 APPLICABLE CONSTRUCTION NOTE OF THE RESUBMITTAL.
  
  
  
 3) THERE ARE INDICATIONS OF WORK INVOLVING EXIT ACCESS,
 EXITS AND EXIT DISCHARGES.
  
 PLEASE REVIEW THESE AREAS AND PROVIDE THE ALTERNATE
 EXITS PLANS AND ROUTES SHOULD THESE AREAS BE
 UNACCESSIBLE TO THE PUBLIC AT ANY TIME DURING THE
 PROJECT.
  
 PROVIDE APLLICABLE LIFE SAFETY PLANS WITH DETAILS.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
  