| Plan Review Notes For Permit 19090543 |
| Permit Number |
19090543 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-09-23 15:04:13 | 1) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | | SPECIFICATIIONS FOR THE HEAT PUMP. THE HEAT PUMP SHALL | | | HAVE A MINIMUM COP OF 4.0 PER THE FBC-ENERGY | | | SEC.R403.10.5, WPB AMEND. TO FBC SEC. 107.2.1. | | | 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | | SPECIFICATION SHEETS FOR THE MAIN DRAIN. THA MAXIMUM | | | GPM DETERMINED BY THE TOTAL DYNAMIC HEAD AND THE POOL | | | PUMP CURVE SHALL NOT EXCEED THE MAXIMUM GPM FLOW | | | THROUGH THE MAIN DRAIN PER APSP 7, WPB AMEND. TO FBC | | | SEC. 107..2.1. | | | 3) PLOT THE TDH AND FLOW ON THE POOL PUMP CURVE.WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|