2019-12-11 18:13:35PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
  
 1) IF YOU DO NOT WISH TO APPLY FOR A SEPARATE PERMIT AS
 NOTED ON SHEET S-2 OF THE APPROVED PLANS, YOU HAVE TWO
 OTHER OPTIONS THAT ARE ACCEPTABLE. NUMBER ONE IS TO
 REVISE SHEET S-2 AND REMOVE THE NOTE AND CORRECT THE
 DIMENSIONS. NUMBER TWO IS TO PROVIDE A SIGNED AND
 SEALED LETTER FROM THE ENGINEER OF RECORD THAT SIGNED
 SHEET S-2, WHICH STATES THAT THE CHILLER SUPPORT SHOWN
 ON SHEET S-2 IS INCLUDED UNDER PERMIT #17121030 AND THE
 DIMENSIONS ARE REVISED AS SHOWN IN THE STRUCTURAL
 CALCULATION DOCUMENTS. ON SHEET S-2 OF THE APPROVED
 PLANS THERE ARE NOTES THAT INDICATE THE CHILLER SUPPORT
 WILL BE UNDER A SEPARATE PERMIT. THEREFORE, THESE
 DOCUMENTS ARE REQUIRED TO BE SUBMITTED AS A SEPARATE
 PERMIT. THIS SUBMITTAL NUMBER CAN BE CHANGED TO A
 PERMIT NUMBER. YOU WILL NEED TO HAVE THE CONTRACTOR
 THAT IS INSTALLING THE CHILLER STAND FILL OUT A PERMIT
 APPLICATION AND SUBMIT IT WITH THE OTHER DOCUMENTS. FBC
 105.1
  
 2) COMPLIED.
  
 3) SINCE BOTH THE 2014 AND 2017 EDITIONS OF THE FBC
 REFERENCE ASCE 7 - 10 FOR STRUCTURAL DESIGN, THE 2017
 FBC IS ACCEPTABLE. THE PROJECT ASSOCIATED WITH THIS
 PERMIT WAS PERMITTED UNDER THE 2014 FBC FIFTH EDITION.
 THEREFORE, TO RETAIN CONSISTENCY THE DOCUMENTS FOR THIS
 PERMIT SHOULD USE THE SAME DESIGN CRITERIA. FBC 107.2.1
  
 4) SEE COMMENT NUMBER 1. THE NOTES ON SHEET S-2 OF THE
 APPROVED PLANS SPECIFY THAT THE CHILLER WILL BE MOUNTED
 ON A 4'-2" X 6'-3" WALL MOUNTED METAL PLATFORM 7'-6"
 AFF AND A WIND PRESSURE OF 96 PSF (ASD). THE
 ENGINEERING DRAWINGS ARE IN CONFLICT WITH THIS
 INFORMATION. THE APPROVED PLANS OR PROPOSED ENGINEERING
 WILL HAVE TO BE REVISED TO CORRECT THE DIFFERENCES AND
 REFLECT ACTUAL LOCATION OF THE PLAT FORM STAND. FBC
 107.2.1
  
 5) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
  