2019-09-17 15:43:44PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
  
 1) SHEET S-2 OF THE APPROVED PLANS THERE ARE NOTES THAT
 INDICATE THE CHILLER SUPPORT WILL BE UNDER A SEPARATE
 PERMIT. THEREFORE, THESE DOCUMENTS ARE REQUIRED TO BE
 SUBMITTED AS A SEPARATE PERMIT. THIS SUBMITTAL NUMBER
 CAN BE CHANGED TO A PERMIT NUMBER. YOU WILL NEED TO
 HAVE THE CONTRACTOR THAT IS INSTALLING THE CHILLER
 STAND FILL OUT A PERMIT APPLICATION AND SUBMIT IT WITH
 THE OTHER DOCUMENTS. FBC 105.1
  
 2) THE ENGINEERED DOCUMENTS THAT WERE SUBMITTED ARE
 SIGNED AND SEALED BY AN ARCHITECT. AN ARCHITECT IS ONLY
 ALLOWED TO SIGN AND SEAL ENGINEERING THAT IS INCIDENTAL
 TO THEIR ARCHITECTURAL PRACTICE.
 ARCHITECTS
 SEC. 481.229 (4)?NOTWITHSTANDING THE PROVISIONS OF THIS
 PART OR OF ANY OTHER LAW, NO REGISTERED ENGINEER WHOSE
 PRINCIPAL PRACTICE IS CIVIL OR STRUCTURAL ENGINEERING,
 OR EMPLOYEE OR SUBORDINATE UNDER THE RESPONSIBLE
 SUPERVISION OR CONTROL OF THE ENGINEER, IS PRECLUDED
 FROM PERFORMING ARCHITECTURAL SERVICES WHICH ARE PURELY
 INCIDENTAL TO HIS OR HER ENGINEERING PRACTICE, NOR IS
 ANY REGISTERED ARCHITECT, OR EMPLOYEE OR SUBORDINATE
 UNDER THE RESPONSIBLE SUPERVISION OR CONTROL OF SUCH
 ARCHITECT, PRECLUDED FROM PERFORMING ENGINEERING
 SERVICES WHICH ARE PURELY INCIDENTAL TO HIS OR HER
 ARCHITECTURAL PRACTICE. HOWEVER, NO ENGINEER SHALL
 PRACTICE ARCHITECTURE OR USE THE DESIGNATION
 ?ARCHITECT? OR ANY TERM DERIVED THEREFROM, AND NO
 ARCHITECT SHALL PRACTICE ENGINEERING OR USE THE
 DESIGNATION ?ENGINEER? OR ANY TERM DERIVED THEREFROM.
  
 3) THE PROJECT ASSOCIATED WITH THIS PERMIT WAS
 PERMITTED UNDER THE 2014 FBC FIFTH EDITION. THEREFORE,
 TO RETAIN CONSISTENCY THE DOCUMENTS FOR THIS PERMIT
 SHOULD USE THE SAME DESIGN CRITERIA. FBC 107.2.1
  
 4) THE NOTES ON SHEET S-2 OF THE APPROVED PLANS SPECIFY
 THAT THE CHILLER WILL BE MOUNTED ON A 4'-2" X 6'-3"
 WALL MOUNTED METAL PLATFORM 7'-6" AFF AND A WIND
 PRESSURE OF 96 PSF (ASD). THE ENGINEERING DRAWINGS ARE
 IN CONFLICT WITH THIS INFORMATION. THE APPROVED PLANS
 OR PROPOSED ENGINEERING WILL HAVE TO BE REVISED TO
 CORRECT THE DIFFERENCES AND REFLECT ACTUAL LOCATION OF
 THE PLAT FORM STAND. FBC 107.2.1
  
 5) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
  
  
  
  
  
  
  
  
  
  