Plan Review Notes For Permit 19090493
Permit Number 19090493
Review Stop M
Sequence Number 1
Notes
Date Text
2019-10-03 12:11:36 
 1ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19090493
 10/3/19
  
 CODES IN EFFECT:
  
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEMS IN ACCORDANCE WITH ACCA MANUAL S AND J-
 SECTION R403.6.1 FBC EC.
  
 2) THERE ARE DISCEPANCIES IN THE PLANS CONCERNING THE
 GARAGE DOOR OPENINGS: A) THE ENERGY EFFICIENCY FORM
 R405-2017 SHOWS WOOD GARAGE DOORS, SHEET A-1 SHOWS THEM
 AS GLASS WINDOWS IN THE SCHEDULE, SHEET A-2 SHOWS THE
 DOOR OPENINGS TO REMAIN U.N.O. PLEASE CORRECT THE PLANS
 AND THE CALCULATIONS.
  
 3) ENERGY FORM 405-2017 INDICATES 2079 SF NEW
 CONDITIONED AREA, HOWEVER SHEET A-1 LISTS THE PROPOSED
 NEW AREAS UNDER AIR AT 1297 SF WITH THE FIRST FLOOR
 AREA LISTED AT 188 SF. BASED ON THE PLAN THE ENTIRE
 GARAGE AREA WILL BE CONDITIONED. PLEASE CORRECT THE
 DISCREPANCIES.
  
 4) MP-1: REFER TO SECTION R403.3.6 FBC EC- THE AIR
 HANDLER SHALL NOT BE INSTALLED IN THE ATTIC ONLY IF THE
 FOLLOWING CONDITIONS ARE MET:
  
 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
  
 2 .A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT
 DOWN THE UNIT WHEN THE CONDENSATION DRAIN IS NOT
 WORKING PROPERLY.
  
 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
  
 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16-POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD:
  
 NOTICE TO HOMEOWNER
 A PART OF YOUR AIR-CONDITIONING SYSTEM, THE AIR
 HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER, EFFICIENT
 AND ECONOMIC OPERATION OF THE AIRCONDITIONING SYSTEM,
 YOU MUST ENSURE THAT REGULAR MAINTENANCE IS PERFORMED.
 YOUR AIR-CONDITIONING SYSTEM IS EQUIPPED WITH ONE OR
 BOTH OF THE FOLLOWING: (1) A DEVICE THAT WILL ALERT YOU
 WHEN THE CONDENSATION DRAIN IS NOT WORKING PROPERLY OR
 (2) A DEVICE THAT WILL SHUT DOWN THE SYSTEM WHEN THE
 CONDENSATION DRAIN IS NOT WORKING. TO LIMIT POTENTIAL
 DAMAGE TO YOUR HOME, AND TO AVOID DISRUPTION OF
 SERVICE, IT IS RECOMMENDED THAT YOU ENSURE PROPER
 WORKING ORDER OF THESE DEVICES BEFORE EACH SEASON OF
 PEAK OPERATION.
  
 5) MP-1: PLEASE NOTE THAT MAKEUP AIR MAY BE REQUIRED
 FOR THE DRYER IN THE CLOSET. PLEASE REVIEW THE
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS AND CORRECT THE PLAN IF REQUIRED- SEE
 SECTION M1502.1 FBC R
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  