| 2019-10-07 13:30:22 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. SHEET CS-1 AND E-1STATE THE 2010 NEC AS THE BASIS |
| | CODE FOR DESIGN, WHICH IS NOT THE CURRENT CODE. PROVIDE |
| | CORRECTION. FBC PREFACE (ALSO SEE CURRENT CODES ABOVE) |
| | 2. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE, |
| | INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF |
| | SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE |
| | E3602.2 |
| | 3. PROVIDE ACCURATE LOAD CALCULATION FOR PANEL B AND |
| | PANEL C, INCLUDE EXISTING AND NEW LOADS TO CONFIRM |
| | CAPACITY IS ADEQUATE. PANEL C IS SHOWN AS BEING FED |
| | FROM PANEL B, WHICH ACCORDING TO PANEL SCHEDULE ONLY |
| | HAS A 50 AMP SERVICE. DEMAND FACTORS ARE NOT PERMITTED |
| | TO BE USED ON FEEDERS LESS THAN 100 AMPS. NEC 215.2, |
| | 220, 408.30; FBC RE E3602.2, E3602.2.1 |
| | 4. PLAN REFERENCES A PANEL GC. WHERE IS THIS PANEL, IT |
| | IS NOT SHOWN ON PLAN OR RISER DIAGRAM? ALSO, THERE ARE |
| | 2 PANEL B SHOWN IN RISER DIAGRAM. PROVIDE ACCURATE |
| | RISER DIAGRAM OF EXISTING SERVICE. NEC 215.5; WPB FBC |
| | 107.2.1 |
| | 5. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE |
| | OUTLETS IN GARAGE INCLUDING THE GARAGE DOOR OPENERS. |
| | PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2 |
| | 6. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE |
| | OUTLETS IN BATHROOM. PROVIDE CORRECTION. NEC 210.8; FBC |
| | RE E3902.1 |
| | 7. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| | 210.8(D); FBC RE E3902.10 |
| | 8. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| | SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| | KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| | PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| | RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| | SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS |
| | INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES. |
| | SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION. |
| | PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902; |
| | FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE. |
| | 9. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 |
| | 10. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE. |
| | FBC EC C405.1, R404.1 |
| | 11. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED |
| | PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING |
| | ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS |
| | NEW INSTALLATIONS. A NOTE FOR AREAS NOT SHOWN ON PLAN |
| | WILL SUFFICE. FBC RE R314.3, R315.1; WPB FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |