| 2019-10-03 18:23:32 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1- ACCORDING TO SEC. R301.2.1.4 FBC-RESIDENTIAL THIS |
| | BUILDING IS LOCATED IN EXPOSURE "D" NOT "C". REVISE THE |
| | DESIGN CRITERIA SHOWN ON SHEET A-3 AT THE BOTTOM LEFT |
| | OF THE PAGE. REVISE THE BUILDING EXPOSURE AND ALL THE |
| | DESIGN WIND PRESSURES ACCORDINGLY. |
| | |
| | 2- SPECIFY CARBON MONOXIDE ALARMS BY THE BEDROOMS AS |
| | REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL |
| | |
| | 3- BASED ON THE EXTERIOR ELEVATIONS PROVIDED IT LOOKS |
| | LIKE THE SECOND FLOOR WINDOW SILL OF THE OPERABLE |
| | WINDOWS IS LOCATED LESS THAN 24 INCHES ABOVE THE |
| | FINISHED FLOOR. NEED TO PROVIDE WINDOW FALL PROTECTION |
| | AS REQUIRED BY SEC. R312.2 FBC-RESIDENTIAL |
| | |
| | 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | HANDRAILS SHOWING COMPLIANCE WITH SEC. R311.7.8 |
| | FBC-RESIDENTIAL. |
| | |
| | 5- ADDITION IS DESIGNED WITH UNVENTED ATTIC. ARCHITECT |
| | IS SPECIFYING R-30 ICYNENE SPRAY INSULATION. PROVIDE |
| | ICC EVALUATION REPORT (2 COPIES) FOR THE ICYNENE R-30 |
| | INSULATION TO VERIFY COMPLIANCE WITH SEC. R316 |
| | FBC-RESIDENTIAL. |
| | NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN |
| | WRITING PRIOR TO SUBMITTAL TO THIS OFFICE |
| | |
| | 6- REVISE ATTIC ACCESS SIZE SPECIFIED ON THE PARTIAL |
| | SECOND FLOOR PLAN ON SHEET A-1. SEE SEC. R807 |
| | FBC-RESIDENTIAL AND REVISE AS REQUIRED. |
| | |
| | 7- SHEET S-2: |
| | A) TRUSS CONNECTORS ARE NOT CLEAR. CONNECTORS SPECIFIED |
| | ON THE ROOF FRAMING PLAN AND CONNECTORS SPECIFIED ON |
| | THE CONNECTOR SCHEDULE SHEET DON'T MATCH. SEE GIRDER |
| | TRUSS TO TIE BEAM CONNECTION. REVISE AS REQUIRED TO |
| | MATCH AND CLEARLY SPECIFY THE CONNECTOR FOR ALL TRUSS |
| | GIRDERS. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | B) REVISE PLYWOOD SHEATHING NAILING SCHEDULE ON SHEET |
| | S-2. ACCORDING TO SEC. R803.2.3.1 FBC-RESIDENTIAL THE |
| | FASTENER NEED TO BE RING SHANK NAILS. CLEARLY SPECIFY |
| | RING SHANK NAILS ON THE PLYWOOD SHEATHING NAILING |
| | SCHEDULE. |
| | |
| | 8- ENERGY CALCULATIONS SUBMITTED: |
| | REVISE ENERGY CALCULATIONS TO MATCH PLANS. (A)ACCORDING |
| | TO PLANS SUBMITTED THERE IS NOT KITCHEN IN THE |
| | ADDITION. (B) REVISE CEILING R-VALUE TO MATCH PLANS. |
| | PROVIDE THE NAME OF THE BUILDER. SEC. R101.5.1.1.2 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | 9- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS |
| | REQUIRED BY SEC. 107.2.1.1 CITY AMENDMENTS. IF |
| | SPECIFYING SCREWS, THEN SPECIFY SIZE AND NUMBER OF |
| | SCREWS. IF SPECIFYING ROOF TILE ADHESIVE, THEN SPECIFY |
| | PADDY SIZE AND PRODUCT APPROVAL IS REQUIRED. |
| | |
| | 10-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO |
| | INSTALLATION TO AVOID CONFLICTS/DELAYS) |
| | |
| | A)ALL WINDOWS SPECIFIED ON PLANS. |
| | B) ALL EXTERIOR DOORS SPECIFIED ON PLANS. |
| | C) WINDOW MULLIONS AS SHOWN ON PLANS. AND REQUIRED: |
| | CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY |
| | COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES. |
| | D)ROOF TILE AND CLEARLY MARK ROOF TILE FASTENING METHOD |
| | AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS. |
| | E)ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF |
| | RECORD. |
| | |
| | 11- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| | REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE |
| | DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| | DRAWINGS/DOCUMENTS FOR REFERENCE. |
| | |
| | |
| | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| | COMMENTS, |