Plan Review Notes
Plan Review Notes For Permit 19090477
Permit Number 19090477
Review Stop E
Sequence Number 2
Notes
Date Text
2019-10-31 09:35:45CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PANEL SCHEDULE STATES THAT THE PANEL IS RATED FOR
 125 AMPS. LOAD CALCULATION STATES THE LOAD IS 141 AMPS,
 SO THE PANEL IS NOT RATED FOR THE LOAD. PROVIDE
 CORRECTION. NEC 408.30 (NOT CORRECTED. RISER DIAGRAM
 SHOWS A 125 AMP DISCONNECT WITH #1 WIRE FEEDING PANEL
 A. BASED ON LOAD CALCULATION PROVIDED, THIS DISCONNECT
 AND WIRE WOULD BE OVERLOADED AND IS NOT SIZED PROPERLY.
 PROVIDE CORRECTION.)
 2. CORRECTED.
 3. IS THIS A NEW SERVICE? PROVIDE CLARIFICATION. WPB
 FBC 107.2.1 (NOT CLARIFIED.)
 4. IF SERVICE IS NEW OR BEING REBUILT, PROVIDE
 AVAILABLE SHORT CIRCUIT CALCULATION FOR SERVICE
 INCLUDING INFORMATION FROM THE POWER COMPANY STATING
 WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE
 SERVICE TO CONFIRM THE STATED AIC RATING OF THE SERVICE
 EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC RE
 E3606.3 (NOT CLARIFIED, NOT PROVIDED.)
 5. CORRECTED.
 6. CORRECTED.
  
 NEW COMMENT:
  
 7. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS (PANEL A AND PANEL B) TO
 CONFIRM CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2,
 220, 408.30; FBC RE E3602.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  