| Plan Review Notes For Permit 19090477 |
| Permit Number |
19090477 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-09-20 11:04:36 | 1) THE ENERGY CALCULATIONS SHOW THE EF OF THE WATER | | | HEATER AS .92. AS OF 4/16/2015, THE MINIMUM EF OF WATER | | | HEATERS SHALL BE .96 PER 10 CFR SEC.430.32. | | | 2) THE SUBMITTED SANITARY RISER SHOWS NO FIXTURES. SHOW | | | PROPOSED CHANGES TO THE SANITARY SYSTEM ON THE SANITARY | | | RISER DIAGRAM. WPB AMEND. TO FBC SEC. 107.2.1. | | | 3) THE PLANS SHOW A STACKED WASHER AND DRYER. THE WATER | | | SUPPLY VALVES FOR THE WASHER SHALL BE ACCESSIBLE PER | | | 2017 FBC-PLUMBING SEC.606.3. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|