| 2019-09-24 13:59:12 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PANEL SCHEDULE STATES THAT THE PANEL IS RATED FOR |
| | 125 AMPS. LOAD CALCULATION STATES THE LOAD IS 141 AMPS, |
| | SO THE PANEL IS NOT RATED FOR THE LOAD. PROVIDE |
| | CORRECTION. NEC 408.30 |
| | 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY |
| | SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, |
| | 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, |
| | E3609.3; WPB FBC 107.2.1 |
| | 3. IS THIS A NEW SERVICE? PROVIDE CLARIFICATION. WPB |
| | FBC 107.2.1 |
| | 4. IF SERVICE IS NEW OR BEING REBUILT, PROVIDE |
| | AVAILABLE SHORT CIRCUIT CALCULATION FOR SERVICE |
| | INCLUDING INFORMATION FROM THE POWER COMPANY STATING |
| | WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE |
| | SERVICE TO CONFIRM THE STATED AIC RATING OF THE SERVICE |
| | EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC RE |
| | E3606.3 |
| | 5. ONLY ONE SERVICE PER RESIDENTIAL ADDRESS IS |
| | PERMITTED. PROVIDE CORRECTION AND/OR CLARIFICATION. WPB |
| | FBC 107.2.1; NEC 230.2; FBC RE E3601.2 |
| | 6. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR |
| | SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE |
| | EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |