| Plan Review Notes For Permit 19090403 |
| Permit Number |
19090403 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-12-10 06:08:12 | PLUMBING 2ND REVIEW**DENIED**19090403 | | | 1) SHT. AE501 TOILET DETAIL SHOWS SIDE GRAB BAR OVERALL | | | AS 52? AND NOT THE REQUIRED MIN OF 54?. FBC-ACC 604.5.1 | | | 2) PROVIDE THE GREASE INTERCEPTOR SIZING CALCULATIONS | | | BASE ON YOUR PDI G 101 . FBC 107.3.5 | | | 3) PROVIDE GREASE INTERCEPTOR INSTALLATION MANUAL. FBC | | | 107.1 | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH (CGA SOLUTIONS) | | | 561-248-2703 | | | [email protected] | | | | | 2019-12-03 09:08:40 | TIM HUNT IS REVIEWING REMOTELY |
|