| 2019-12-10 06:08:44 | GAS 2ND REVIEW**DENIED**19090403 |
| | 1) TERMINATION OF WATER HEATER VENT DOES NOT SHOW |
| | ANCHORING OR INTAKE VENT. PLEASE CLARIFY. FBC 107.2.1 |
| | 2) DEFERRED SUBMITTAL ON GAS EQUIPMENT IS NOT PERMITTED |
| | AND MUST BE SUBMITTED FOR THIS PLAN REVIEW. AS I |
| | EXPLAINED OVER THE PHONE AFTER THE 1ST REVIEW THIS |
| | WOULD NEED TO BE APPROVE BY THE CHIEF PLUMBING |
| | INSPECTOR (TIM LARGE) WHICH TO DATE HAS NOT HAPPENED. |
| | SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3.GAS |
| | APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC |
| | SEC.305.1 |
| | 3) PROVIDE SIZING CHARTS FOR SYSTEM AFTER THE PRESSURE |
| | REDUCING REGULATORS. SUBMIT TWO COPIES OF THE |
| | APPLICABLE SIZING TABLES USED TO SIZE THE GAS SYSTEM OR |
| | PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH |
| | SIZING TABLE(S) FROM THE GAS CODE OR OTHER STANDARD |
| | THAT WERE USED IN THE DESIGN OF THIS GAS SYSTEM. REFER |
| | TO THE 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND |
| | TABLES 402.4 (1) THRU 402.4 (37) |
| | 4) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE INSIDE |
| | OF THE BUILDING SHALL BE APPROVED FOR INDOOR |
| | INSTALLATION. PROVIDE VENTING OF EACH REGULATOR. DOES |
| | NOT MATTER WHO IS SUPPLYING THEM BUT THE INSTALLATION |
| | MANUAL IS REQUIRED FOR THIS REVIEW. 2017 FGC SEC.410.1 |
| | |
| | |