| Date |
Text |
| 2019-11-26 09:54:23 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19090385 |
| | ADD: 1913 S DIXIE HWY SUITE: 400 |
| | CONT: PM DEVELOPMENT |
| | TEL: 561-889-5874 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: TUESDAY NOV. 26/2019 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. |
| | |
| | 2) OK. |
| | |
| | 3- OK |
| | |
| | ORIGINAL COMMENT: |
| | 4) PROVISO: IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY |
| | ON THE PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER |
| | OF RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 |
| | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| | LOADS AND SPACING USED IN THE TESTS. |
| | |
| | RESPONSE: |
| | PRODUCT APPROVALS WERE NOT REVIEWED BY THE ARCHITECT OF |
| | RECORD AND INFORMATION ON PRODUCT APPROVAL IS NOT |
| | MARKED SHOWING THE SPECIFIC SIZE, TYPE OF GLAZING |
| | MULLION SIZE, ETC AS REQUESTED. |
| | NOTE: THIS INFORMATION MAY BE SUBMITTED LATER AS |
| | DEFERRED SUBMITTAL BUT BEFORE INSPECTIONS. |
| | |
| | 5) OK |
| | |
| | 6) OK |
| | |
| | 7) COMPLIED. |
| | |
| | ORIGINAL COMMENT: |
| | 8) NEW COMMENT. SHEET LS1.01 & A1.01 BOTH SHOW A NEW |
| | FRONT ENTRY DESIGN WITH A DOUBLE DOOR LOBBY/ VESTIBULE |
| | SYSTEM. WITH THIS TYPE OF SYSTEM YOU STILL WILL NEED TO |
| | SHOW COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY CODE |
| | 404.2.6 DOORS IN SERIES AND FIGURE 404.2.6. THE |
| | DISTANCE BETWEEN TWO HINGED OR PIVOTED DOORS IN SERIES |
| | AND GATES IN SERIES SHALL BE 48 INCHES MINIMUM PLUS THE |
| | WIDTH OF DOORS OR GATES SWINGING INTO THE SPACE. |
| | |
| | RESPONSE: |
| | NOT ADDRESSED. AND, THERE IS A NEW COMMENT THAT |
| | UNFORTUNATELY WAS OVERLOOKED REGARDING THE MANEUVERING |
| | CLEARANCE REQUIRED AT MANUAL DOORS. IT LOOKS LIKE THE |
| | CORRIDOR LEADING TO OFFICE #105 IS TOO NARROW. |
| | ACCORDING TO SEC. 404.2.4.1 AND FIGURE 404.2.4.1(J) FBC |
| | ACCESSIBILITY, THE MINIMUM CORRIDOR WIDTH NEEDS TO BE |
| | AT LEAST 42 INCHES. REVISE PLANS AS REQUIRED. |
| | |
| | ORIGINAL COMMENT: |
| | 9) NEW COMMENT. SHEET LS1.01 & A1.01 BOTH SHOW A NEW |
| | FRONT ENTRY DESIGN WITH STRUCTURAL WING WALLS AND |
| | CEILING THAT WILL BE SUBJECT TO EXTERIOR WEATHER |
| | CONDITIONS RAIN AND WIND. PLEASE PROVIDE THE MATERIALS |
| | THIS EXTERIOR WALL & CEILING WILL BE CONSTRUCTED FROM. |
| | 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1 THE ADMINISTRATIVE CODE 107.2.1.2 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | RESPONSE: |
| | NOT ADDRESSED. |
| | |
| | ORIGINAL COMMENT: |
| | 10) THE NEWLY FORM SET OF PLANS ARE NOT COMPLETE, |
| | MISSING THE COVERSHEET WITH INDEX OF DRAWINGS AND THE |
| | D.01 DEMOLITION SHEET AND NOTES. 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 THE |
| | ADMINISTRATIVE CODE 107.2.1.2 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | RESPONSE: |
| | NOT ADDRESSED. NEED TO COORDINATE SET OF PLANS. PROVIDE |
| | COMPLETE SET OF PLANS. |
| | |
| | |
| | 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| | COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |