Plan Review Notes
Plan Review Notes For Permit 19090385
Permit Number 19090385
Review Stop P
Sequence Number 2
Notes
Date Text
2019-11-05 12:40:54CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
 1. REGARDING THE REQUIRED WATER FOUNTAINS AS REQUIRED
 PER FBC PL TABLE 403.2 COMPLYING WITH FBC ACC, PER WPB
 FBC 107.2, PROVIDE DETAIL OF DF SHOWING COMPLIANCE WITH
 FBC ACC 306, TOE AND KNEE CLEARANCES AND 602, SPOUTS
 HEIGHT AND LOCATION (SEE BELOW)
 A. 602.4 SPOUT HEIGHT. SPOUT OUTLETS SHALL BE 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 B. 602.5 SPOUT LOCATION. THE SPOUT SHALL BE LOCATED 15
 INCHES MINIMUM FROM THE VERTICAL SUPPORT AND 5 INCHES
 MAXIMUM FROM THE FRONT EDGE OF THE UNIT, INCLUDING
 BUMPERS.
 C. 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS. SPOUT
 OUTLETS OF DRINKING FOUNTAINS FOR STANDING PERSONS
 SHALL BE 38 INCHES MINIMUM AND 43 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
 2. REGARDING DETAILS A1.03/2 AND A1.03/3, THE MAXIMUM
 HEIGHT OF 2'-10" (34") SHALL BE SHOWN TO THE TOP OF THE
 SINK RIM, NOT TO THE TOP OF THE COUNTER TO COMPLY WITH
 FBC ACC 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE
 INSTALLED WITH THE FRONT "OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE" 34 INCHES (865 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
 3.RE: SANITARY ISOMETRIC; PER FBC PL 905.3 AND 905.4,
 DRY VENTS CONNECTING TO A HORIZONTAL DRAIN SHALL
 CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL
 DRAINPIPE AND RISE VERTICALLY TO A POINT NOT LESS THAN
 6" ABOVE THE FLOOD LEVEL RIM OF THE FIXTURES BEING
 VENTED
 4. RE: WATER DISTRIBUTION ISOMETRIC
 A. PER FBC PL TABLE 604.5, URINAL REQUIRES 3/4" COLD
 WATER SUPPLY
 B. PER FBC PL TABLE 604.5, SERVICE SINK AND SINK EACH
 REQUIRES 1/2" HOT AND COLD WATER SUPPLY.
 C. PER WPB FBC 107.2.1, PROVIDE CALCULATIONS USED IN
 SIZING OF WATER DISTRIBUTION. INCLUDE A PLUMBING
 FIXTURE SCHEDULE INDICATING THE DEMAND.
 D. PROVIDE NOTE, "WATER DISTRIBUTION SHALL BE OF A
 MATERIAL THAT COMPLIES WITH FBC PL TABLE 605.4."
 E. IS THERE AN EXISTING WATER SUPPLY? SHOW WHERE WATER
 SUPPLY IS COMING FROM AND THE SIZE.SHOW EXISTING
 BACKFLOW PREVENTER OR PROVIDE A NEW ONE TO CONFORM TO
 THE REQUIREMENTS OF FBC PL 608. PER WPB FBC 107.2.1,
 SHOW LOCATION ON FLOOR PLAN AS WELL AS RISER DIAGRAM.
 5. RE: P1.01, PLUMBING NOTE 14; INSERT THE WORDS "FROM
 LAVATORIES" BETWEEN THE WORDS "DELIVERED" AND "THROUGH"
 TO SHOW COMPLIANCE WITH FBC PL 416.5.
 6. REGARDING THE REQUIRED WATER HEATER DETAIL, DETAIL
 FOR WATER HEATER PIPING TO COMPLY WITH FBC PL 607.3,
 PROVIDE THERMAL EXPANSION CONTROL AND FBC PL 504, SHOW
 ANTI SIPHON DEVICE, I.E, .COLD DIP TUBE OR VACUUM
 RELIEF VALVE. PROVIDE AIR GAP FOR RELIEF LINE AT
 TERMINATION TO SERVICE SINK OR YOU MAY DISCHARGE TO
 REQUIRED PAN WITH AN AIR GAP; DRAIN SHALL BE SIZED AND
 OF A MATERIAL THAT COMPLIES WITH FBC PL TABLE 605.4.
 SHOW REQUIRED PAN AND DRAIN AND DISCHARGE TO SINK WITH
 AIR GAP; DRAIN SHALL BE SIZED AND OF A MATERIAL THAT
 COMPLIES WITH FBC PL TABLE 605.4. .
 ADDITIONALLY, PER WPB FBC 107.2.1, PROVIDE ELECTRICAL
 CHARACTERISTICS OF WATER HEATER.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19090385 1913 S DIXIE HWY
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved