Plan Review Notes
Plan Review Notes For Permit 19090385
Permit Number 19090385
Review Stop P
Sequence Number 1
Notes
Date Text
2019-09-27 14:09:371ST REVIEW: 19090385
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. A WATER FOUNTAIN IS REQUIRED PER FBC PL TABLE 403.2
 COMPLYING WITH FBC ACC
 602.4 SPOUT HEIGHT. SPOUT OUTLETS SHALL BE 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 602.2 CLEAR FLOOR SPACE. UNITS SHALL HAVE A CLEAR FLOOR
 OR GROUND SPACE COMPLYING WITH 305 POSITIONED FOR A
 FORWARD APPROACH AND CENTERED ON THE UNIT. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS. SPOUT
 OUTLETS OF DRINKING FOUNTAINS FOR STANDING PERSONS
 SHALL BE 38 INCHES MINIMUM AND 43 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
  
 2. THE LAVATORY OUTSIDE THE ACCESSIBLE STALL SHALL
 COMPLY WITH FBC ACC 606.2/606.3
  
 3. PLEASE SHOW THE REQUIRED CLEAR FLOOR SPACE AT THE
 BREAK ROOM SINK. PER FBC ACC 606.2
  
 4. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE. PER FBC ACC 609.4
  
 5. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE. PER FBC ACC 604.5.2
  
 6. SHOW COMPLIANCE FOR THE LAVATORY'S. PER FBC ACC
 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 7. ON THE SANITARY ISOMETRIC THE TOILETS AND URINAL ARE
 NOT VENTED THEY SHALL BE VENTED BEFORE CONNECTING TO
 THE BUILDING DRAIN WITH A SEPARATE VENT OR WET VENT
 SYSTEM COMPLYING WITH FBC PL 912.1
  
 8. SHT. P1.01 NOTE 11 ALL FIXTURES SHALL COMPLY WITH
 FLORIDA BUILDING CODE ACCESSIBILITY 2017 6TH EDITION.
  
 9. PLEASE PROVIDE WATER ISOMETRIC DRAWING. PER WPB
 AMEND TO FBC 107.3.5.1.3(13)
  
 10. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 11. A BACK FLOW IS REQUIRED ON SUPPLY TO ANY ICE MAKER
 OR COFFEE MACHINE. PER FBC PL 608.3 608.16.10
  
 12. PROVIDE DETAIL FOR WATER HEATER PIPING TO COMPLY
 WITH FBC ACC 607.3, 504,
  
 13. PROVIDE DETAIL FOR WATER HEATER PLATFORM SHOW WHAT
 TYPE OF ANCHORS WILL BE USED IT SHALL HOLD 300LB +. PER
 WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]