| 2019-09-27 14:09:37 | 1ST REVIEW: 19090385 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. A WATER FOUNTAIN IS REQUIRED PER FBC PL TABLE 403.2 |
| | COMPLYING WITH FBC ACC |
| | 602.4 SPOUT HEIGHT. SPOUT OUTLETS SHALL BE 36 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | 602.2 CLEAR FLOOR SPACE. UNITS SHALL HAVE A CLEAR FLOOR |
| | OR GROUND SPACE COMPLYING WITH 305 POSITIONED FOR A |
| | FORWARD APPROACH AND CENTERED ON THE UNIT. KNEE AND TOE |
| | CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED. |
| | 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS. SPOUT |
| | OUTLETS OF DRINKING FOUNTAINS FOR STANDING PERSONS |
| | SHALL BE 38 INCHES MINIMUM AND 43 INCHES MAXIMUM ABOVE |
| | THE FINISH FLOOR OR GROUND. |
| | |
| | 2. THE LAVATORY OUTSIDE THE ACCESSIBLE STALL SHALL |
| | COMPLY WITH FBC ACC 606.2/606.3 |
| | |
| | 3. PLEASE SHOW THE REQUIRED CLEAR FLOOR SPACE AT THE |
| | BREAK ROOM SINK. PER FBC ACC 606.2 |
| | |
| | 4. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL |
| | POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE |
| | THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING |
| | SURFACE. PER FBC ACC 609.4 |
| | |
| | 5. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES |
| | MINIMUM ON THE OTHER SIDE. PER FBC ACC 604.5.2 |
| | |
| | 6. SHOW COMPLIANCE FOR THE LAVATORY'S. PER FBC ACC |
| | 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING |
| | WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE |
| | AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED |
| | WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER |
| | SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | |
| | 7. ON THE SANITARY ISOMETRIC THE TOILETS AND URINAL ARE |
| | NOT VENTED THEY SHALL BE VENTED BEFORE CONNECTING TO |
| | THE BUILDING DRAIN WITH A SEPARATE VENT OR WET VENT |
| | SYSTEM COMPLYING WITH FBC PL 912.1 |
| | |
| | 8. SHT. P1.01 NOTE 11 ALL FIXTURES SHALL COMPLY WITH |
| | FLORIDA BUILDING CODE ACCESSIBILITY 2017 6TH EDITION. |
| | |
| | 9. PLEASE PROVIDE WATER ISOMETRIC DRAWING. PER WPB |
| | AMEND TO FBC 107.3.5.1.3(13) |
| | |
| | 10. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 |
| | |
| | 11. A BACK FLOW IS REQUIRED ON SUPPLY TO ANY ICE MAKER |
| | OR COFFEE MACHINE. PER FBC PL 608.3 608.16.10 |
| | |
| | 12. PROVIDE DETAIL FOR WATER HEATER PIPING TO COMPLY |
| | WITH FBC ACC 607.3, 504, |
| | |
| | 13. PROVIDE DETAIL FOR WATER HEATER PLATFORM SHOW WHAT |
| | TYPE OF ANCHORS WILL BE USED IT SHALL HOLD 300LB +. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |