Plan Review Notes
Plan Review Notes For Permit 19090385
Permit Number 19090385
Review Stop M
Sequence Number 1
Notes
Date Text
2019-09-27 17:11:101ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19090385
 9/27/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.01: THE SUPPLY DUCTS ARE MISLABLED AS
 RETURN DUCTS (RD). PLEASE CORRECT- SECTION 107.2.1 WPB.
  
 2) M1.01: INDICATE THE DIFFUSER AND RETURN GRILL
 DIMENSIONS.
  
 3) M1.01: PLEASE CLEARLY IDENTIFY THE MAIN DUCT. THE
 PLAN DOES NOT CLEARLY SHOW HOW ALL AIR IS BEING
 RETRUNED TO THE AIR HANDLER- SECTION- 601.6 FBC M.
  
 4) M1.01: PLEASE PROVIDE THE MAKE AND MODEL OF THE
 EXISTING AIR HANDLER, AND IT'S COOLING AND HEATING
 CAPACITIES IN BTUH AND KW- SECTION 107.2.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  