| 2019-09-27 17:11:10 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19090385 |
| | 9/27/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M1.01: THE SUPPLY DUCTS ARE MISLABLED AS |
| | RETURN DUCTS (RD). PLEASE CORRECT- SECTION 107.2.1 WPB. |
| | |
| | 2) M1.01: INDICATE THE DIFFUSER AND RETURN GRILL |
| | DIMENSIONS. |
| | |
| | 3) M1.01: PLEASE CLEARLY IDENTIFY THE MAIN DUCT. THE |
| | PLAN DOES NOT CLEARLY SHOW HOW ALL AIR IS BEING |
| | RETRUNED TO THE AIR HANDLER- SECTION- 601.6 FBC M. |
| | |
| | 4) M1.01: PLEASE PROVIDE THE MAKE AND MODEL OF THE |
| | EXISTING AIR HANDLER, AND IT'S COOLING AND HEATING |
| | CAPACITIES IN BTUH AND KW- SECTION 107.2.1 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |