| Plan Review Notes For Permit 19090385 |
| Permit Number |
19090385 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-10-04 12:44:42 | .FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) NEED TO SUBMIT A RISER DIAGRAM | | | PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC 215.5; | | | FBC 107.2.1 | | | | | | 2) LOAD CALCULATION IS DONE AS RESIDENCE. | | | PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING | | | AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS | | | ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3 | | | | | | 3) ENERGY CONSERVATION CODE NOT ADDRESSED | | | PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: | | | 8.4.2. FBC CE 405.7.1 | | | | | | PROVIDE LIGHTING CONTROL PER FBC ENERGY CODE. FBC CE | | | 405.2.2.2 | | | |
|