| 2019-10-01 15:04:03 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PLAN SHOWS NEW 125 AMP PANEL. WHERE IS THIS PANEL |
| | FED FROM? PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY |
| | SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, |
| | 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, |
| | E3609.3; WPB FBC 107.2.1 |
| | 2. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE THE |
| | NEW PANEL IS FED FROM, INCLUDE EXISTING AND NEW LOADS |
| | TO CONFIRM CAPACITY OF SERVICE IS ADEQUATE. THE 3 WATTS |
| | PER SQUARE FOOT IS NOT INCLUDED IN THE CALCULATION |
| | PROVIDED. NEC 215.2, 220, 408.30; FBC RE E3602.2 |
| | 3. BASED ON COMMENT 2, THE 125 AMP PANEL IS OVERLOADED. |
| | PROVIDE CORRECTION. NEC 408.30; BC RE E3706.1 |
| | 4. FLOOR PLAN SHOWS AN AC LOCATED DIRECTLY IN FRONT OF |
| | THE ELECTRICAL SERVICE. PROVIDE CORRECTION TO MAINTAIN |
| | CLEARANCE PER CODE. NEC 110.26; FBC RE E3405 |
| | 5. PLAN IS NOT CLEAR ON THE EXISTING ELECTRICAL |
| | SSERVICE. IF A NEW SERVICE IS TO BE INSTALLED, PROVIDE |
| | AVAILABLE SHORT CIRCUIT CALCULATION FOR SERVICE |
| | INCLUDING INFORMATION FROM THE POWER COMPANY STATING |
| | WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE |
| | SERVICE TO CONFIRM THE STATED AIC RATING OF THE SERVICE |
| | EQUIPMENT IS ADEQUATE. PROVIDE AIC RATING OF ELECTRICAL |
| | SERVICE EQUIPMENT. NEC 110.3, 110.9, 110.10; FBC RE |
| | E3606.3 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |