| 2019-10-02 14:52:39 | BUILDING VERTICAL SHELL. RESIDENTIAL (R2) BUILDING |
| | REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- COVER SHEET 001-A-0.0 WAS NOT SIGNED AND SEALED. |
| | NEED DIGITAL SIGNATURE. |
| | 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND |
| | SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | 2- ALL THE STRUCTURAL DRAWINGS SPECIFY WOOD TRUSSES. |
| | ALL THE ARCHITECTURAL PLANS ON BUILDING PERMIT 19030235 |
| | SPECIFY METAL TRUSSES. THIS IS A TYPE 1B BUILDING. THE |
| | BUILDING ELEMENTS ON A TYPE 1B CONSTRUCTION BUILDING |
| | NEED TO BE OF NONCOMBUSTIBLE MATERIALS. SEC. 602.2 |
| | FBC-BUILDING. REVISE ALL STRUCTURAL DRAWINGS. REVISE |
| | ALL STRUCTURAL PLANS AND DETAILS THAT ARE SPECIFYING |
| | WOOD TRUSSES OR WOOD LEDGERS AND REVISE CORRESPONDING |
| | STRUCTURAL CONNECTIONS AS WELL. SEC. 1601.1 |
| | FBC-BUILDING. COORDINATE WITH THE ARCHITECTURAL PLANS. |
| | |
| | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| | COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |
| | REMAINDER FOR FOUNDATION PERMIT APPROVED UNDER PERMIT |
| | #19030239. |
| | |
| | |
| | FOUNDATION PERMIT APPROVED WITH PROVISO |
| | 1- SHEET A-2.1: REVISE TYPO ON SIZE OF GRATE ON THE |
| | GRATE DETAIL. CALCULATIONS SPECIFY 4.75' NOT 14.75'. |
| | AND PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR THE |
| | CONSTRUCTION OF THE GRATES. SEE SEC. 2.7.2.1 ASCE/SEI |
| | 24-14. |
| | NOTE: TAKE INTO CONSIDERATION ACCESS TO THE CREATED |
| | CRAWL SPACE. |
| | 2- REVISE/CLARIFY "CONSTRUCTION DRAWINGS" ELEVATION |
| | CERTIFICATE. SEE REDLINED ELEVATION CERTIFICATE. |
| | ADDITIONAL ELEVATION CERTIFICATES WILL BE REQUIRED FOR |
| | BUILDING UNDER CONSTRUCTION AND FINISHED CONSTRUCTION. |
| | 3- SURVEYOR'S NOTE #13 SPECIFIES BASE FLOOD ELEVATION |
| | OF 12.7 FEET. SPECIFY IF N.A.V.D 1988 OR N.G.V.D 1929. |
| | 4- BASED ON THE HEIGHT OF THE BUILDING, A BARRIER AND |
| | COVERED WALKWAY FOR PROTECTION OF PEDESTRIANS WILL BE |
| | REQUIRED. SEC. 3306.1 FBC-BUILDING. |
| | 5- ART IN PUBLIC PLACES. PLEASE CONTACT MS. SYBILLE |
| | WELTER ART IN PUBLIC PLACES COORDINATOR 822-1515 |
| | E-MAIL: [email protected] FOR MORE INFORMATION. |
| | |
| | |
| | |