| Date |
Text |
| 2019-09-27 17:17:21 | 09/27/2019 2ND GAS REVIEW **DENIED** WITH COMMENTS |
| | |
| | NOTE: A FULL AND COMPREHENSIVE PLAN REVIEW COULD NOT BE |
| | ACCOMPLISHED AT THIS TIME DUE TO THE QUALITY OF THE |
| | SUBMITTED PLANS. ADDITIONAL COMMENTS MAY BE GENERATED |
| | ON THE RESUBMITTAL REVIEW. |
| | |
| | 1. THE ADDRESS OF THE PROJECT OR RESIDENCE MUST BE ON |
| | PLAN IN FULL, NUMBER, ST. CITY AND ZIP CODE PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | 2. GAS RISER DIAGRAM NEED TO BE ALL IN ONE PAGE, PLEASE |
| | SHOW REGULATOR, UNIONS, DRIP LEGS VALVES, HARD CAP OFF |
| | FOR FUTURE AND CLEARLY SHOWS THE LENGTH OF ALL CUT |
| | SECTIONS OF PIPE PER THE 2017 FBC RES. SECS. G2413.4.1, |
| | G2413.4.2. |
| | 3. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE ISOMETRIC PER THE 2017 FBC RES. SEC. G2413.2. |
| | 4. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| | AHEAD OF EACH MP REGULATOR PER THE 2017 FBC RES. SEC. |
| | G2420.4. |
| | 5. THIS TANKLESS UNIT CALLS FOR A LOWER WATER COLUMN |
| | AND IF THE SERVICE METER DISCHARGES IS A 2 PSI WATER |
| | COLUMN REQUIRING A REGULATOR FOR THIS UNIT AS PER |
| | MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES. |
| | SEC. G2421.1. |
| | 6. SUBMIT SPEC THAT SHOW THE POOL HEATER SHALL HAVE A |
| | MINIMUM THERMAL EFFICIENCY OF 82% PLEASE PER THE 2017 |
| | FBC-ENERGY SEC. R403.10.4. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 1:00 PM TO 4:00 PM |
| | [email protected] |
| | |