| 2019-12-17 17:50:57 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19090272 |
| | 12/17/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODEWPB- WEST PALM BEACH |
| | AMENDMENTS TO THE FBC SIXTH EDITION 2017 |
| | NFPA 110- 2018 |
| | NFPA 37- 2018 |
| | NFPA 30- 2018 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | THE PLANS ARE NOT VALID FOR REVIEW BECAUSE THEY HAVE |
| | COPIED ELECTRONIC SEALS AND SIGNATURES. PLEASE PROVIDE |
| | ORIGINAL RAISED OR INK SEALS AND SIGNATURES- SECTION |
| | 471.025 AND SECTION 61G15.23002 FAC. |
| | |
| | PLEASE NOTE THAT THE INSTALLATION IOF THE 660 GALLON |
| | FUEL TANK REQUIRES APPROVAL BY PALM BEACH COUNTY |
| | DEPARTMENT OF ENVIRONMENTAL RESOURCES. |
| | |
| | COMMENTS BELOW FROM THE 1ST REVIEW LISTED BELOW WILL BE |
| | MARKED AS OK OR NOT COMPLIED. |
| | |
| | 1) OK. NOTE- SHEETS SP1.03 & M1.2.1 REQUIRE ORIGINAL |
| | SIGNATURES AND SEALS BY THE DESIGN PROFESSIONALS. |
| | |
| | 2) OK |
| | |
| | 3) OK |
| | |
| | 4) NOT COMPLIED. SUBMIT THE SPECS FOR THE ENGINE |
| | EXHAUST PIPE- SECTION 8.1.1 NFPA 37. |
| | |
| | A) INDICATE THE DIAMETER OF THE EXHAUST PIPE AND THE |
| | TOTAL RUN LENGTH OF THE PIPE ON SHEET M1.2.1A. |
| | |
| | B) PROVIDE THE CLEARANCE DISTANCES FROM THE EXHAUST |
| | PIPE DISCHARGE TO GRADE AND TO THE PROPERTY LINE- |
| | SECTION 501.3.1(2) FBC M. |
| | |
| | C) PROVIDE BACKPRESSURE CALCULATIONS FOR THE EXHAUST |
| | PIPING AND SILENCER, AND VERIFY THE BACKPRESSURE DOES |
| | NOT EXCEED THE MAXIMUM 10 KPA ALLOWABLE BACKPRESSURE |
| | PER THE GENERATOR MANUFACTURER. |
| | |
| | IN RESPONSE TO COMMENT #4 THE AOR HAS PROVIDED NOTES IN |
| | HIS RESPONSE LETTER TO ADDRESS THE COMMENTS, BUT NO |
| | INFORMATION HAS BEEN PROVIDED ON PLAN SHEET M1.2.1.A. |
| | |
| | 5) OK |
| | |
| | 6) OK |
| | |
| | 7) NOT COMPLIED. SHEET M.1.2.1A: THE RADIATOR EXHAUST |
| | AIR DISCHARGE SHALL BE DUCTED OUTDOORS OR TO AN |
| | EXTERIOR OPENING BY A 2-HOUR FIRE-RATED TRANSFER |
| | SYSTEM- SECTION 7.7.4.2 NFPA 110. PLEASE NOTE THAT THE |
| | SOUNDLINED DISHARGE PLENUM IS NOT A 2-HOUR FIRE-RATED |
| | TRANSFER SYSTEM PER THE SUBMITTED DRAWINGS. |
| | |
| | 8) NOT COMPLIED. REFER TO SECTION 7.7.1 NFPA 110- 2016 |
| | AND VERIFY THAT THE VENTILATION AIRFLOW IN THE |
| | GENERATOR/TANK (EPS) ROOM IS DESIGNED TO LIMIT THE |
| | MAXIMUM AIR TEMPERATURE IN THE ROOM TO THE MAXIMUM |
| | AMBIENT AIR TEMPERATURE REQUIRED BY THE GENERATOR |
| | MANUFACTURER. CONSIDERATION SHALL BE GIVEN TO ALL THE |
| | HEAT EMITTED TO THE ROOM BY THE ENERGY CONVERTER, |
| | EXHAUST PIPES, |
| | AND ALL OTHER HEAT PRODUCING EQUIPMENT- SECTION |
| | 7.7.1.1. DESIGN OF THE HEATING, COOLING, AND |
| | VENTILATION SYSTEM SHALL AMONG OTHER THINGS, INCLUDE |
| | PROVISIONS FOR FACTORS SUCH AS HEAT, COLD, HUMIDITY, |
| | LOUVERS, ETC.- SECTION 7.7.7. |
| | |
| | 9) NOT COMPLIED. M1.2.1A: GENERATOR/FUEL TANK ROOM |
| | EXHAUST SYSTEM: |
| | |
| | A) PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE |
| | GENERATOR/TANK (EPS) ROOM, AND PROVIDE AN EQUIPMENT |
| | SCHEDULE FOR EF-2- SECTION 502.4.2 FBC M. |
| | |
| | B) THE EF-2 EXHAUST DUCT SHALL RUN INDEPENDENTLY, AND |
| | SHALL BE ENCLOSED IN 2-HR FIRE-RATED CONSTRUCTION FROM |
| | THE PENETRATION OF THE WALL TO THE EXHAUST OUTLET- |
| | SECTIONS 501.3, 510.2, 510.6.7 |
| | |
| | C) INDICATE THE TYPE AND GAGE OF THE EXHAUST DUCTWORK- |
| | SECTION 510.9 FBC M. |
| | |
| | D) PLEASE NOTE THAT EXHAUST SYSTEM SHALL RUN |
| | CONTINUOUSLY- SECTIONS 4.1.2.1.3 & 6.3.6.5.1 NFPA 37, |
| | AND SECTION 502.4.2 FBC. |
| | |
| | DEFINITION OF ENVIRONMENTAL AIR DOES NOT INCLUDE |
| | EXHAUST FROM A GENERATOR/FUEL TANK ROOM. PLEASE REFER |
| | TO SECTION 510.2 FBC M, SECTION 6.3.6.5.1 NFPA 37, AND |
| | SECTION 24.10.1 NFPA 30. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |