| 2019-09-30 08:17:18 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19090266 |
| | ADD: 5600 N FLAGLER DR. SUITE: 905 |
| | CONT: AOA CONSTRUCTION LLC |
| | TEL: 561-660-3504 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. SEPT. 30/ 2019 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE NOTE THAT THE ELECTRONIC SHEET SUBMITTED EX |
| | ENGINEERING EXPRESS IS A PAPER COPY THAT WAS UPLOADED, |
| | NOT AN ORIGINAL ELECTRONIC SHEET. THE DIGITAL SIGNATURE |
| | DOES NOT OPEN FOR VERIFICATION. |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A |
| | SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE |
| | OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON |
| | ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | 2) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 |
| | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| | LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 3) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE ENGINEER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 4) PLEASE NOTE NO FLOOR PLAN WAS SUBMITTED INDICATING |
| | THE LOCATION OF THIS UNIT IN RELATIONSHIP TO THE |
| | BUILDING. THE ENGINEERING SHEET THAT WAS SUBMITTED |
| | INDICATES THE UNIT IN QUESTION IS AN INTERIOR UNIT IN |
| | WALL ZONE 4. THE PRODUCT APPROVAL 17-0420.12 A |
| | MIAMI-DADE NOA FOR SERIES SGD-770 ALUMINUM SLIDING |
| | GLASS DOOR W/ 90 DEGREE & 135 DEGREE CORNERS, THIS |
| | COULD SUGGEST AN END UNIT AND OUTSIDE CORNER? |
| | W 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE |
| | 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. THIS IS A |
| | STAND-ALONE PERMIT. NO-OTHER PERMITS CAN BE REFERENCED. |
| | |
| | 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |