| 2019-10-15 09:11:32 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19090257 |
| | ADD: 5600 N. FLAGLER DR. SUITE: 905 |
| | CONT: AMERICA REMODELING |
| | TEL: 561-843-3782 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: TUES. OCT. 15/ 2019 |
| | ACTION: DENIED |
| | |
| | |
| | *************4X FEE / NOTICE!!!!! FLORIDA STATUTE |
| | 553.80(2)(B) ******************* |
| | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | |
| | |
| | |
| | 1) 2ND REVIEW/ 2ND REQUEST. PLEASE NOTE WHEN |
| | CONTRACTORS ARE TAKING THE EXCEPTION TO THE |
| | REQUIREMENTS FOR DESIGN PROFESSIONALS TO CREATE PLANS |
| | THE CONTRACTOR (QUALIFIER) HAS TO SIGN THEIR NAME AND |
| | PRINT THEIR NAME IN THE TITLE BLOCK AS WELL AS THE |
| | LICENSE NUMBER FOR WHICH TRADE THEY ARE LICENSED. |
| | PLEASE NOTE UNLESS THE CGC ALSO HAS AN ELECTRICAL |
| | LICENSE THEY CANNOT TAKE RESPONSIBILITY FOR THE |
| | ELECTRICAL PLAN. |
| | |
| | 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, OF THE ADMINISTRATIVE CODE SECTION |
| | 107.3.4.2. CERTIFICATIONS BY CONTRACTORS. |
| | |
| | 2) SHEET A-1 & A-2 BOTH INDICATE THAT THE FLOORING WILL |
| | BE REMOVED AND REPLACED THROUGH-OUT THE ENTIRE UNIT. |
| | THE PLANS DO NOT INDICATE AS TO WHAT TYPE OF FLOORING |
| | IS TO BE INSTALLED. PLEASE NOTE: |
| | |
| | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| | 2017) |
| | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS (NOT SALES BROCHURES) |
| | SHOWING COMPLIANCE WITH: |
| | |
| | 2A) 2ND REVIEW/ 2ND REQUEST. FBC-B 2017 1207.3 |
| | STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. |
| | |
| | 2B) 2ND REVIEW/ 2ND REQUEST. FBC-B 2017 1207.2 |
| | AIR-BORNE SOUND. WALLS, PARTITIONS AND FLOOR/CEILING |
| | ASSEMBLIES SEPARATING DWELLING UNITS FROM EACH OTHER OR |
| | FROM PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND |
| | TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45 IF |
| | FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E 90. |
| | |
| | 2C) 2ND REVIEW/ 2ND REQUEST. FLAME SPREAD- FBC-B 2017 |
| | 603.1. EXCEPTION 2. INSULATION INSTALLED BETWEEN A |
| | FINISHED FLOOR AND SOLID DECKING WITHOUT INTERVENING |
| | AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| | OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 3) 2ND REVIEW/ 2ND REQUEST. BUILDING WAS BUILT IN 1978. |
| | ASBESTOS COMMERCIAL: PLEASE PROVIDE A SIGNED |
| | ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD, |
| | STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF |
| | ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF |
| | HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT |
| | NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL |
| | INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE |
| | FOUND ON THEIR WEBSITE: |
| | |
| | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE |
| | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- |
| | RENOVATION.HTML |
| | |
| | 901 EVERNIA STREET |
| | WEST PALM BEACH, FL 33401 |
| | (561) 837-5900 ASBESTOS PROGRAM COORDINATOR |
| | |
| | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO |
| | [email protected]. THE INFORMATION SHOULD BE IN PDF |
| | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE |
| | THE PERMIT NUMBER AND ASBESTOS IN THE SUBJECT LINE. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |