| Date |
Text |
| 2019-09-30 09:09:12 | |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19090257 |
| | ADD: 5600 N. FLAGLER DR. SUITE: 905 |
| | CONT: AMERICA REMODELING |
| | TEL: 561-843-3782 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. SEPT. 30/ 2019 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE NOTE WHEN CONTRACTORS ARE TAKING THE |
| | EXCEPTION TO THE REQUIREMENTS FOR DESIGN PROFESSIONALS |
| | TO CREATE PLANS THE CONTRACTOR (QUALIFIER) HAS TO SIGN |
| | THEIR NAME AND PRINT THEIR NAME IN THE TITLE BLOCK AS |
| | WELL AS THE LICENSE NUMBER FOR WHICH TRADE THEY ARE |
| | LICENSED. PLEASE NOTE UNLESS THE CGC ALSO HAS AN |
| | ELECTRICAL LICENSE THEY CANNOT TAKE RESPONSIBILITY FOR |
| | THE ELECTRICAL PLAN. |
| | |
| | 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, OF THE ADMINISTRATIVE CODE SECTION |
| | 107.3.4.2. CERTIFICATIONS BY CONTRACTORS. |
| | |
| | 2) SHEET A-1 & A-2 BOTH INDICATE THAT THE FLOORING WILL |
| | BE REMOVED AND REPLACED THROUGH-OUT THE ENTIRE UNIT. |
| | THE PLANS DO NOT INDICATE AS TO WHAT TYPE OF FLOORING |
| | IS TO BE INSTALLED. PLEASE NOTE: |
| | |
| | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| | 2017) |
| | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS (NOT SALES BROCHURES) |
| | SHOWING COMPLIANCE WITH: |
| | |
| | 2A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 2B) FBC-B 2017 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 2C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 3) BUILDING WAS BUILT IN 1978. ASBESTOS COMMERCIAL: |
| | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE |
| | CONTRACTOR, ON LETTERHEAD, STATING THAT THE |
| | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM |
| | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH |
| | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE |
| | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS |
| | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: |
| | |
| | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE |
| | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- |
| | RENOVATION.HTML |
| | |
| | 901 EVERNIA STREET |
| | WEST PALM BEACH, FL 33401 |
| | (561) 837-5900 ASBESTOS PROGRAM COORDINATOR |
| | |
| | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO |
| | [email protected]. THE INFORMATION SHOULD BE IN PDF |
| | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE |
| | THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |