| 2019-09-16 05:52:19 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY PERSON |
| | RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FS |
| | 481.229; WPB FBC 107.2.1, 107.3.5.1.2 |
| | |
| | 2. RECEPTACLE REQUIRED OUTSIDE OF DWELLING LOCATED AT |
| | BOTH FRONT AND REAR OF STRUCTURE. NEC 210.52E1 |
| | |
| | 3.WALL SPACING FOR RECEPTACLES NOT PER CODE. RECEPTACLE |
| | REQUIRED WITHIN 6FT OF DOOR OPENING THEN EVERY 12FT |
| | THEREAFTER AND ON WALLS GREATER THAN 2FT IN LENGTH. NEC |
| | 210.52A1&2 |
| | |
| | 4.PROVIDE ACCURATE LOAD CALCULATION FOR ENTIRE SERVICE |
| | (MAIN HOUSE LOADS ALSO) TO INCLUDE ALL LOADS BOTH NEW |
| | AND EXISTING. LOAD CALCULATION PROVIDED ONLY SHOWS NEW |
| | LOADS AND IS NOT ACCURATE. NEC 220; FBC RE E3602.2 |
| | |
| | 5. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC EC R404.1 |
| | |
| | 6. MINISPLIT OCP INCORRECT. PLANS SAYS EQUIPMENT NEEDS |
| | 15AMP OCP BUT HAS 20AMP OCP ON PANEL SCHEDULE. PROVIDE |
| | ACCURATE PANEL SCHEDULE. FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |