Plan Review Notes
Plan Review Notes For Permit 19090254
Permit Number 19090254
Review Stop E
Sequence Number 1
Notes
Date Text
2019-09-16 05:52:19ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FS
 481.229; WPB FBC 107.2.1, 107.3.5.1.2
  
 2. RECEPTACLE REQUIRED OUTSIDE OF DWELLING LOCATED AT
 BOTH FRONT AND REAR OF STRUCTURE. NEC 210.52E1
  
 3.WALL SPACING FOR RECEPTACLES NOT PER CODE. RECEPTACLE
 REQUIRED WITHIN 6FT OF DOOR OPENING THEN EVERY 12FT
 THEREAFTER AND ON WALLS GREATER THAN 2FT IN LENGTH. NEC
 210.52A1&2
  
 4.PROVIDE ACCURATE LOAD CALCULATION FOR ENTIRE SERVICE
 (MAIN HOUSE LOADS ALSO) TO INCLUDE ALL LOADS BOTH NEW
 AND EXISTING. LOAD CALCULATION PROVIDED ONLY SHOWS NEW
 LOADS AND IS NOT ACCURATE. NEC 220; FBC RE E3602.2
  
 5. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
  
 6. MINISPLIT OCP INCORRECT. PLANS SAYS EQUIPMENT NEEDS
 15AMP OCP BUT HAS 20AMP OCP ON PANEL SCHEDULE. PROVIDE
 ACCURATE PANEL SCHEDULE. FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  