Plan Review Notes For Permit 19090177
Permit Number 19090177
Review Stop P
Sequence Number 2
Notes
Date Text
2019-12-12 15:16:101) ALL BACKFLOWS MUST BE LEAD FREE AND BE ON THE LIST
 OF APPROVED DEVICES BY THE UNIVERSITY OF SOUTHERN
 CALIFORNIA FOUNDATION FOR CROSS CONNECTION CONTROL AND
 HYDRAULIC RESEARCH PER THE CITY OF WEST PALM BEACH
 CROSS CONNECTION CONTROL MANUAL AS ADOPTED BY CITY
 ORDINANCE.
 2) THE HOSE BIBB TO THE DUMPSTER SHALL BE EQUIPPED WITH
 A SHUTOFF VALVE PER 2017 FBC-PLUMBING SEC.606.2 AND BE
 EQUIPPED WITH A VACUUM BREAKER PER SEC.605.15.4.2.
 3) SUBMIT A STORM DRAIN RISER FOR THE TOWER
 ROOFS.HORIZONTAL AND VERTICAL DRAIN PIPING SHALL COMPLY
 WITH 2017 FBC-PLUMBING SEC.1106.2, 1106.3. PARAPET
 WALLS SHALL BE INCLUDED IN THE CALCULATIONS PER SEC.
 1106.4.
 4) PROVIDE A SCUPPER DETAIL SHOWING LENGTH AND WIDTH
 DIMENSIONS. COMPLY WITH 2017 FBC -BUILDING SEC.
 1503.4.2 AND 1503.4.2.1.
 5) RAINWATER LEADERS SHALL DISCHARGE A MINIMUM OF ONE
 FOOT FROM THE BUILDING PER 2017 FBC-BUILDING SEC.
 1503.7. SEE SHEET A8.04, DETAILS #5 & #6.
 6) SHT. P1.01 - BACKFLOW PREVENTERS SHALL BE LOCATED AS
 CLOSE TO THE METER AS POSSIBLE. CONTACT THE UTILITIES
 DEPARTMENT AT 561-822-2244 TO DISCUSS AN ALTERNATE
 LOCATION.
 7) SHT. P1.01 SHOWS 5 BAYS IN THIS BUILDING BUT SHTS.
 PD-2 SHOWS 2 BAYS, SHT. PD-3 SHOWS 3 AND PD-4 SHOWS 3
 BAYS. CLARIFY.PLEASE CHECK THE WS SHEETS ALSO.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692