| Plan Review Notes For Permit 19090177 |
| Permit Number |
19090177 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-12-12 15:16:10 | 1) ALL BACKFLOWS MUST BE LEAD FREE AND BE ON THE LIST | | | OF APPROVED DEVICES BY THE UNIVERSITY OF SOUTHERN | | | CALIFORNIA FOUNDATION FOR CROSS CONNECTION CONTROL AND | | | HYDRAULIC RESEARCH PER THE CITY OF WEST PALM BEACH | | | CROSS CONNECTION CONTROL MANUAL AS ADOPTED BY CITY | | | ORDINANCE. | | | 2) THE HOSE BIBB TO THE DUMPSTER SHALL BE EQUIPPED WITH | | | A SHUTOFF VALVE PER 2017 FBC-PLUMBING SEC.606.2 AND BE | | | EQUIPPED WITH A VACUUM BREAKER PER SEC.605.15.4.2. | | | 3) SUBMIT A STORM DRAIN RISER FOR THE TOWER | | | ROOFS.HORIZONTAL AND VERTICAL DRAIN PIPING SHALL COMPLY | | | WITH 2017 FBC-PLUMBING SEC.1106.2, 1106.3. PARAPET | | | WALLS SHALL BE INCLUDED IN THE CALCULATIONS PER SEC. | | | 1106.4. | | | 4) PROVIDE A SCUPPER DETAIL SHOWING LENGTH AND WIDTH | | | DIMENSIONS. COMPLY WITH 2017 FBC -BUILDING SEC. | | | 1503.4.2 AND 1503.4.2.1. | | | 5) RAINWATER LEADERS SHALL DISCHARGE A MINIMUM OF ONE | | | FOOT FROM THE BUILDING PER 2017 FBC-BUILDING SEC. | | | 1503.7. SEE SHEET A8.04, DETAILS #5 & #6. | | | 6) SHT. P1.01 - BACKFLOW PREVENTERS SHALL BE LOCATED AS | | | CLOSE TO THE METER AS POSSIBLE. CONTACT THE UTILITIES | | | DEPARTMENT AT 561-822-2244 TO DISCUSS AN ALTERNATE | | | LOCATION. | | | 7) SHT. P1.01 SHOWS 5 BAYS IN THIS BUILDING BUT SHTS. | | | PD-2 SHOWS 2 BAYS, SHT. PD-3 SHOWS 3 AND PD-4 SHOWS 3 | | | BAYS. CLARIFY.PLEASE CHECK THE WS SHEETS ALSO. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|