2019-12-10 14:00:211ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19090177
 12/10/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENTS #1 & #3 FROM THE 1ST REVIEW HAVE NOT BEEN
 ADEQUATELY ADDRESSED BY THE EOR. THE EOR STATES IN HIS
 RESPONSE TO THE COMMENTS THAT THE PROPOSED PROJECT IS A
 "COLD DARK SHELL" AND THE AC AND ENERGY CALCULATIONS
 WILL BE PROVIDED BY EACH NEW TENANT. PLEASE REFER TO
 SECTION C101.4.2 EXEMPT BUILDINGS FBC EC.
  
 SUBSECTION C101.4.2.3 LOW ENERGY BUILDINGS AS DESCRIBED
 IN SECTION C402.1.1:
  
 SUCH BUILDINGS SHALL NOT CONTAIN ELECTRICAL, PLUMBING
 OR MECHANICAL SYSTEMS WHICH HAVE BEEN DESIGNED TO
 ACCOMODATE THE FUTURE INSTALLATION OF HEATING OR
 COOLING EQUIPMENT.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE
 RESTAURANT RTU- AC SYSTEMS- SECTION C403.2.1 FBC EC AND
 SECTION 312.1 FBC M.
  
 3) SUBMIT AN ENERGY COMPLIANCE REPORT USING EITHER THE
 PRESCRIPTIVE OR PERFORMANCE BASED COMPLIANCE PATH AS
 REQUIRED BY SECTION C101.5 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  