| 2019-12-10 14:00:21 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19090177 |
| | 12/10/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | COMMENTS #1 & #3 FROM THE 1ST REVIEW HAVE NOT BEEN |
| | ADEQUATELY ADDRESSED BY THE EOR. THE EOR STATES IN HIS |
| | RESPONSE TO THE COMMENTS THAT THE PROPOSED PROJECT IS A |
| | "COLD DARK SHELL" AND THE AC AND ENERGY CALCULATIONS |
| | WILL BE PROVIDED BY EACH NEW TENANT. PLEASE REFER TO |
| | SECTION C101.4.2 EXEMPT BUILDINGS FBC EC. |
| | |
| | SUBSECTION C101.4.2.3 LOW ENERGY BUILDINGS AS DESCRIBED |
| | IN SECTION C402.1.1: |
| | |
| | SUCH BUILDINGS SHALL NOT CONTAIN ELECTRICAL, PLUMBING |
| | OR MECHANICAL SYSTEMS WHICH HAVE BEEN DESIGNED TO |
| | ACCOMODATE THE FUTURE INSTALLATION OF HEATING OR |
| | COOLING EQUIPMENT. |
| | |
| | 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE |
| | RESTAURANT RTU- AC SYSTEMS- SECTION C403.2.1 FBC EC AND |
| | SECTION 312.1 FBC M. |
| | |
| | 3) SUBMIT AN ENERGY COMPLIANCE REPORT USING EITHER THE |
| | PRESCRIPTIVE OR PERFORMANCE BASED COMPLIANCE PATH AS |
| | REQUIRED BY SECTION C101.5 FBC EC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |