Plan Review Notes
Plan Review Notes For Permit 19090177
Permit Number 19090177
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2019-12-02 10:59:58PROVISO: IT APPEARS THAT BASED ON THE PROPOSED LOCATION
 AND SITE DRAWINGS OF THE DUMPSTERS, THAT DOORS COULD
 POSSIBLY IMPEDE FIRE DEPARTMENT ACCESS. PLEASE REVIEW
 THE FOLLOWING CODES IN REFERENCE TO FIRE DEPARTMENT
 ACCESS, AND CLEARANCE:
  
 18.2.3.1 REQUIRED ACCESS.
 18.2.3.1.1 APPROVED FIRE DEPARTMENT ACCESS ROADS SHALL
 BE PROVIDED FOR EVERY FACILITY, BUILDING, OR PORTION OF
 A BUILDING HEREAFTER CONSTRUCTED OR RELOCATED.
 18.2.3.1.2 FIRE DEPARTMENT ACCESS ROADS SHALL CONSIST
 OF ROADWAYS, FIRE LANES, PARKING LOT LANES, OR A
 COMBINATION THEREOF.
 18.2.3.2.1 A FIRE DEPARTMENT ACCESS ROAD SHALL EXTEND
 TO WITHIN 50 FT (15 M) OF AT LEAST ONE EXTERIOR DOOR
 THAT CAN BE
 OPENED FROM THE OUTSIDE AND THAT PROVIDES ACCESS TO THE
 INTERIOR OF THE BUILDING.
 18.2.3.3 MULTIPLE ACCESS ROADS. MORE THAN ONE FIRE
 DEPARTMENT ACCESS ROAD SHALL BE PROVIDED WHEN IT IS
 DETERMINED BY
 THE AHJ THAT ACCESS BY A SINGLE ROAD COULD BE IMPAIRED
 BY VEHICLE CONGESTION, CONDITION OF TERRAIN, CLIMATIC
 CONDITIONS, OR OTHER FACTORS THAT COULD LIMIT ACCESS.
 18.2.3.4.1.1 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN
 UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FT (6.1 M).
  