| Plan Review Notes For Permit 19090177 |
| Permit Number |
19090177 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-10-15 06:53:19 | PLUMBING 1ST REVIEW**DENIED** | | | 1) PLEASE ADD NOTE TO PLAN BOTH THE GREASE INTERCEPTOR | | | AND THE BACKFLOWS WILL REQUIRE SEPARATE PERMITS. THE | | | BACKFLOWS MUST ALSO ONLY BE INSTALLED BY A LICENSE | | | PLUMBING CONTRACTOR. FBC 105.1, 2017 WPB CROSS | | | CONNECTION MANUAL. | | | 2) PLEASE PROVIDE AN ISOMETRIC DRAWING FOR THE GREASE, | | | SANITARY, STORM, AND WATER. FBC 107.3.5 | | | 3) PROVIDE HOW YOU DETERMINED THE SIZING FOR THE GREASE | | | INTERCEPTOR PER EITHER THE PDI G101 OR FLORIDA | | | ADMINISTRATIVE CODE 64E-6. | | | | | | | | | TIM HUNT | | | PLUMBING EXAMINERS | | | CITY OF WEST PALM BEACH (CGA SOLUTIONS) | | | [email protected] | | | 561-248-2703 | | | |
|