| 2019-10-11 10:10:23 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19090177 |
| | 10/11/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE |
| | RESTAURANT RTU- AC SYSTEMS- SECTION C403.2.1 FBC EC AND |
| | SECTION 312.1 FBC M. |
| | |
| | 2) VERFIY THE NEW RTU'S WILL BE EQUIPPED WITH |
| | AUTOMATICALLY CONTROLLED SHUTOFF DAMPERS FOR O/A- |
| | SECTION C403.2.4.3 FBC EC. |
| | |
| | 3) SUBMIT AN ENERGY COMPLIANCE REPORT USING EITHER THE |
| | PRESCRIPTIVE OR PERFORMANCE BASED COMPLIANCE PATH AS |
| | REQUIRED BY SECTION C101.5 FBC EC. |
| | |
| | 4) INCOMPLETE STRUCTURAL ENGINEERING FOR THE RTU ROOF |
| | OPENINGS, CURB AND CURB CAP ATTACHMENTS AND RTU |
| | MOUNTING. PLEASE PROVIDE COMPLETE DETAILS PER SECTION |
| | 301.15 FBC M. |
| | |
| | 5) SUBMIT A FL. PRODUCTAPPROVAL OR MIAMI-DADE NOA FOR |
| | THE AC CONDENSER STANDS- RULE 9N-3 FAC. PLEASE NOTE |
| | THIS MAY BE A DEFERRED SUBMITTAL IF NECESSARY- SECTION |
| | 107.3.4.1 WPB. |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |