Plan Review Notes
Plan Review Notes For Permit 19090177
Permit Number 19090177
Review Stop M
Sequence Number 1
Notes
Date Text
2019-10-11 10:10:231ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19090177
 10/11/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE
 RESTAURANT RTU- AC SYSTEMS- SECTION C403.2.1 FBC EC AND
 SECTION 312.1 FBC M.
  
 2) VERFIY THE NEW RTU'S WILL BE EQUIPPED WITH
 AUTOMATICALLY CONTROLLED SHUTOFF DAMPERS FOR O/A-
 SECTION C403.2.4.3 FBC EC.
  
 3) SUBMIT AN ENERGY COMPLIANCE REPORT USING EITHER THE
 PRESCRIPTIVE OR PERFORMANCE BASED COMPLIANCE PATH AS
 REQUIRED BY SECTION C101.5 FBC EC.
  
 4) INCOMPLETE STRUCTURAL ENGINEERING FOR THE RTU ROOF
 OPENINGS, CURB AND CURB CAP ATTACHMENTS AND RTU
 MOUNTING. PLEASE PROVIDE COMPLETE DETAILS PER SECTION
 301.15 FBC M.
  
 5) SUBMIT A FL. PRODUCTAPPROVAL OR MIAMI-DADE NOA FOR
 THE AC CONDENSER STANDS- RULE 9N-3 FAC. PLEASE NOTE
 THIS MAY BE A DEFERRED SUBMITTAL IF NECESSARY- SECTION
 107.3.4.1 WPB.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  