Plan Review Notes
Plan Review Notes For Permit 19090177
Permit Number 19090177
Review Stop B
Sequence Number 1
Notes
Date Text
2019-10-16 16:12:28BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19090177
 REVIEWED: OCTOBER 16, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1) 109.3 FBC[AMENDED]I SEE THIS IS SHEEL ONLY, BUT THE
 VALUE STILL SEEMS LOW AT $55.00 PER SQ. FT.
 - PLEASE PROVIDE DOCUMENTATION OF HOW VALUE WAS
 DETERMINED.
  
 2)319 FBC[R] ADDRESS IS NEEDED FOR THIS BUILDING. THE
 PERMIT CANNOT BE ISSUED UNTIL AND ADDRESS HAS BEEN
 ASSIGNED TO THIS BUILDING.
 - PLEASE CALL MICHAEL ORIO BY PHONE AT 561-494-1080, OR
 BY E-MAIL [email protected]
  
 3) 401.2 FBC[CE] APPLICATION. COMMERCIAL BUILDINGS
 SHALL COMPLY WITH ONE OF THE FOLLOWING:
 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1,
 EXCLUDING SECTION 9.4.1.1(G) OF THE STANDARD.
 2. THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN
 ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH
 SECTION C406 AND TENANT SPACES SHALL COMPLY WITH
 SECTION C406.1.1.
 3. THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404,
 C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING
 ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 PERCENT
 OF THE STANDARD REFERENCE DESIGN BUILDING.
 - PLEASE PROVIDE DOCUMENTATION TO SHOW COMPLIANCE WITH
 ENERGY CONSERVATION CODE.
  
 4) MIXED USE FBC[B]508
 1. ACCESSORY OCCUPACY SEE SECTION 508.2.1 THRU 508.2.4
 (AREA LESS THAN 10% OF FLOOR AREA WHERE LOCATED.
 2. NON-SEPARATED OCCUPANCIES SECTION 508.3 THE MOST
 RESTRICTIVE OCCUPANCY APPLIES TO ALL.
 3. SEPARATED OCCUPANCIES SECTION 508.4 USE TABLE
 508.4.(DASH IS THERE TO SAY ANSWER IS PROVIDED
 ALREADY)EXAMPLE:IF LOOKING I TO A, TRY LOOKING A TO I.
 - HOW WILL SEPARATE OCCUPANCIES BE HANDLED?
 NON-SEPARATE OR SEPARATED. IF NON-SEPARATED SEE FBC
 [B]903.2.1.2 IF SEPARATED SHOW THE WALL RATINGS
 REQUIRED IN TABLE 508.4 FOR A-2 FROM M
  
 5) 602.1 FBC[B]SHEET A2.01 STATE THE TYPE OF
 CONSTRUCTION AND THE OCCUPANCY GROUP.
 - PLEASE UPDATE THE FBC CODE REFERENCE IN THE
 PARENTHESIS TO SAY 2017 INSTEAD OF 2014.
  
 6) 704.10 FBC[B] EXTERIOR STRUCTURAL MEMBERS.
 LOAD-BEARING STRUCTURAL MEMBERS LOCATED WITHIN THE
 EXTERIOR WALLS OR ON THE OUTSIDE OF A BUILDING OR
 STRUCTURE SHALL BE PROVIDED WITH THE HIGHEST
 FIRE-RESISTANCE RATING AS DETERMINED IN ACCORDANCE WITH
 THE FOLLOWING:
 1. AS REQUIRED BY TABLE 601 FOR THE TYPE OF BUILDING
 ELEMENT BASED ON THE TYPE OF CONSTRUCTION OF THE
 BUILDING;
 2. AS REQUIRED BY TABLE 601 FOR EXTERIOR BEARING WALLS
 BASED ON THE TYPE OF CONSTRUCTION; AND
 3. AS REQUIRED BY TABLE 602 FOR EXTERIOR WALLS BASED ON
 THE FIRE SEPARATION DISTANCE.
 - STATE THE FIRE RESISTANCE REQ'D FOR BUILDING ELEMENTS
 FROM TABLE 601 FOR TYPE III-B CONSTRUCTION, OR INDICATE
 WHERE THAT INFORMATION IS IN THE PLANS.
  
 7) 107.2.5 FBC[AMENDED] PROVIDE SURVEY OF PROPERTY
 SHOWING EASEMENTS AND DISTANCE FROM PROPERTY LINES TO
 NEW STRUCTURE. SURVEY TO INCLUDE SLAB ELEVATION AND
 SHOW POSITIVE DRAINAGE FROM FOUNDATION.
  
 8) 401.4 FBC[R] PROVIDE SOIL REPORT TO SHOW BEARING
 CAPACITY AND FOUNDATION RECOMMENDATIONS.
  
 9) 107.3.5.3 FBC[AMENDED] PROVIDE SEDIMENT CONTROL TO
 KEEP CONSTRUCTION DEBRIS FROM ENTERING ADJACENT
 PROPERTIES AND STORM DRAINS DURING CONSTRUCTION. YOU
 CAN JUST ADD SILT FENCE DETAIL AND HOW DRAINS ARE
 PROTECTED TO THE DRAINAGE PLAN. SOME ENGINEERING
 STANDARD DETAILS CAN BE USED FROM WPB WEBSITE-POLLUTION
 CONTROL. HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUB
 LIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 10) PAVING AND DRAINAGE PLANS
 - PROVIDE CIVIL PLANS TO SHOW ELEVATIONS AND SLOPES OF
 PARKING, SIDEWALKS AND FINISHED FLOOR SLAB.
  
 11)1609.4.3 FBC[B] EXPOSURE CATEGORIES. AN EXPOSURE
 CATEGORY SHALL BE DETERMINED IN ACCORDANCE WITH THE
 FOLLOWING: EXPOSURE B. FOR BUILDINGS WITH A MEAN ROOF
 HEIGHT OF LESS THAN OR EQUAL TO 30 FEET, EXPOSURE B
 SHALL APPLY WHERE THE GROUND SURFACE ROUGHNESS, AS
 DEFINED BY SURFACE ROUGHNESS B, PREVAILS IN THE UPWIND
 DIRECTION FOR A DISTANCE OF AT LEAST 1,500 FEET. FOR
 BUILDINGS WITH A MEAN ROOF HEIGHT GREATER THAN 30 FEET,
 EXPOSURE B SHALL APPLY WHERE SURFACE ROUGHNESS B
 PREVAILS IN THE UPWIND DIRECTION FOR A DISTANCE OF AT
 LEAST 2,600 FEET OR 20 TIMES THE HEIGHT OF THE
 BUILDING, WHICHEVER IS GREATER.
 EXPOSURE C. EXPOSURE C SHALL APPLY FOR ALL CASES WHERE
 EXPOSURE B OR D DOES NOT APPLY.
 EXPOSURE D. EXPOSURE D SHALL APPLY WHERE THE GROUND
 SURFACE ROUGHNESS, AS DEFINED BY SURFACE ROUGHNESS D,
 PREVAILS IN THE UPWIND DIRECTION FOR A DISTANCE OF AT
 LEAST 5,000 FEET OR 20 TIMES THE HEIGHT OF THE
 BUILDING, WHICHEVER IS GREATER. EXPOSURE D SHALL ALSO
 APPLY WHERE THE GROUND SURFACE ROUGHNESS IMMEDIATELY
 UPWIND OF THE SITE IS B OR C, AND THE SITE IS WITHIN A
 DISTANCE OF 600 FEET OR 20 TIMES THE BUILDING HEIGHT,
 WHICHEVER IS GREATER, FROM AN EXPOSURE D CONDITION AS
 DEFINED IN THE PREVIOUS SENTENCE.
 - STRUCTURAL SHEETS S1 AND S1.1 USE EXPOSURE CATEGORY B
 FOR WIND DESIGN. THIS PROPERTY IS A CATEGORY C AND ALL
 SHEETS THAT REFERENCE CATEGORY B NEED TO BE UPDATED TO
 STATE CATEGORY C.
  
 12) 107.5.3 FBC[AMENDED]PLEASE UPLOAD STRUCTURAL
 CALCULATIONS TO SHOW DESIGN CRITERIA, LOADS AND
 DEFLECTIONS.
  
 13) 107.5.3 FBC[AMENDED]PLEASE ADD MEAN ROOF
 HEIGHT(M.R.H.) TO ELEVATION SHEET A3.01.
 - M.R.H THE TOP OF ROOF DECK
  
 PROVISOS:
 DEFERRED SUBMITTALS-SEE LIST ON SHEET A0.01
 1) ROOF ACCESS LADDER
 2) ROOFING PRODUCT APPROVALS AND APPLICABLE ENGINEERING
 DUE WITH SUB-PERMIT APPLICAION.
 3) EXTERIOR FENESTRATION (WINDOWS, STOREFRONT, DOORS
 AND DRIVE THRU WINDOW)
 4) SEPARATE PERMITS FOR LIGHT POLES/SITE LIGHTING,
 DUMPSTER ENCLOSURE, FIRE ALARM, FIRE SPRINKLER, LOW
 VOLTAGE, ACCESS, LANDSCAPING, IRRIGATION, PARKING LOT,
 CANOPIES AND ALL OTHER ITEMS OTHER THAN BMEP
 5) STEEL JOISTS ENGINEERING TO BE PROVIDED TO INSPECTOR
 PRIOR TO INSTALLATION.
 6) CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM
 SAT-SUN
 - NO RESPONSE REQUIRED. THESE WILL BE ADDED TO THE
 PLANS AT FINAL STAMPING.
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  