| 2019-09-16 10:12:36 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT:19090173 REVISION TO MASTER 19060311 |
| | REVIEWED: SEPTEMBER 16, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | |
| | 1) 107.5.3 FBC[AMENDED]PLEASE PROVIDE A NARRITIVE TO |
| | EXPLAIN WHAT IS OCCURING IN THE REVISION. SHEET D-2 NOW |
| | SHOWS UNIT OPEN TO PREVIOUS AGJACENT TENANT SPACE A12 |
| | AND NOTES CALL TO REMOVE THE NEXT DEMISING WALL. |
| | SHEET A-1 SHOWS REMOVING THE DOOR THAT COMMUNICATED |
| | WITH ADJACENT AND REMOVING WALL IN ADJACENT UNIT. WHY |
| | SHOW NEW SPACE ADDED TO ADJACENT TENANT. |
| | IF SPACE IS ADDED TO THAT UNIT THAN PROVIDE SEPARATE |
| | PERMIT WITH DOCUMENTATION TO SHOW HOW THAT UNIT IS |
| | BEING ALTERED TO ADD ADDITIONAL SPACE TO INCLUDE LIFE |
| | SAFETY AND FLOOR PLAN. |
| | |
| | 2) 107.5.3 FBC[AMENDED]IS CASPER BECOMING LARGER THAN |
| | PREVIOUSLY PERMITTED, OR DOES THE SHEET A-1 PROJECT |
| | AREA INCLUDE AREA FROM THE ADJACENT TENANT. |
| | PROVIDE AN UPDATED OCCUPANT LOAD THAT WAS PREVIOUSLY |
| | FOUND IN MASTER ON SHEET T-001 IF APPLICABLE. |
| | |
| | 3) 107.5.3 FBC[AMENDED]WHAT IS THE CURRENT USE OF |
| | ADDITIONAL SPACE BEING ADDED FOR WHAT TENANT AND THE |
| | PROPOSED USE?(MAY REQUIRE ADDITIONAL PERMIT IF IS |
| | ADDING SPACE TO THE ADJACENT TENANT) |
| | |
| | NOTES: |
| | |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |