Plan Review Notes
Plan Review Notes For Permit 19090079
Permit Number 19090079
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2019-10-04 12:00:52THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) COMPLIED
  
  
  
 2) NOT COMPLIED
  
 THERE ARE NO INDICATIONS OF COMPLAINCE WITH ANY NFPA
 CODES.
  
 THE PROPOSED PROJECT SHALL COMPLY WITH, THE FLORIDA
 FIRE PREVENTION CODES AND ALL OTHER APPLICABLE CODES
 INCLUDING BUT NOT LOMITED TO:
  
 NFPA 110, NFPA 110, STANDARD FOR EMERGENCY AND STANDBY
 POWER SYSTEMS, 2013 EDITION.
 NFPA 37, STANDARD FOR THE INSTALLATION AND USE OF
 STATIONARY
 COMBUSTION ENGINES AND GAS TURBINES, 2015 EDITION.
 NFPA 58, LIQUEFIED PETROLEUM GAS CODE, 2014 EDITION.
  
  
  
 3) NOT COMPLIED - NO DIMENSIONS ARE PROVIDED FROM THE
 PROPERTY LINE.
  
 THERE ARE NO INDICATIONS OF THE LP FUEL SUPPLY LOCATION
 AND OR SIZE ON THE PLAN SHEETS.
  
 PLEASE PROVIDE DETAILS, INCLUDING NEAREST BUILDINGS,
 PROPERTY LINES AND VEHICLE DRIVE PATHS
  
  
  
  
 3A) NEW COMMENT - A LP TANK IS INDICATED.
  
 IS THIS AN UNDERGROUND OR ABOVEGROUND TANK.
  
 PLEASE PROVIDE DETAILS.
  
  
  
  
 4) NOT COMPLIED - NO DIMENSIONS ARE PROVIDED
  
 FOR EXHAUST MIGRATION REVIEW, PLEASE PROVIDE THE
 DIMENSIONS AND LOCATIONS OF WINDOWS, DOORS, SOFFITS OR
 AIR INTAKE EQUIPMENT.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  