Plan Review Notes
Plan Review Notes For Permit 19090079
Permit Number 19090079
Review Stop G
Sequence Number 1
Notes
Date Text
2019-09-16 18:17:0209/16/2019 1ST GAS/LP/TANK REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB PLUMBING PERMIT (GAS) LP BY A LICENSED
 CONTRACTOR IS REQUIRED FOR THE SCOPE OF WORK PER THE
 WPB AMENDMENTS TO THE FBC SEC. 105.1
 2. GAS RISER DIAGRAM REQUIRED PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.5.1.5 (9) COMMERCIAL GAS
 3. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE AND TYPE OF PIPE PER
 2017 FBC FG SECS. 402.4.1, 402.4.2.
 4. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC FG SEC. 402.2.
 5. PLEASE SHOW SHUTOFF VALVES, UNIONS, DRIP LEGS, BTU
 AND REGULATORS ON ISOMETRIC PER THE 2017 FBC FG SEC.
 409.4.
 6. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1? OF
 EITHER SIDE PER THE 2017 FBC FG SEC 410.2.
 7. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC
 FG SEC. 402.4.1.
 8. PLAN ARE TOO SMALL TO READ NOTES, PLANS SHALL BE
 DRAWN TO A MINIMUM 1/8 INCH SCALE ON E.01 PER THE WPB
 AMENDMENT TO FBC SEC. 107.2.1.3 QUALITY OF BUILDING
 PLANS.
 9. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE
 DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM PER THE 2017 FBC FG SEC. 402.
 10. IF A REGULATOR IS REQUIRED SUBMIT MANUFACTURER?S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC FG
 SEC. 410.1.
 11. CLEARLY, INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE GROUND OR BELOW GROUND, AND SHOW THE METHOD OF
 REQUIRED PROTECTION FOR THE LP TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK IS BELOW GROUND IT SHALL BE
 ANCHORED PER NFPA 58 SEC.3-2.2.7 (H). IF ABOVE GROUND,
 THE TANK SHALL BE SECURELY ANCHORED TO WITHSTAND 170
 MPH ULT WIND LOAD PER THE FLORIDA BUILDING CODE. WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 12. SHOW THE DEPTH OF THE LP GAS CONTAINER IF BELOW
 GRADE. COMPLY WITH NFPA 58 SEC. 6.6.6.1.
 13. FOR A CATHODIC PROTECTION SYSTEM SHALL BE REQUIRED
 PER NFPA 58 SECS. 5.2.1.11, 6.6.6.1 (I) AND SHALL BE
 MONITORED PER NFPA 58 SEC.6.6.6.1 (J). SUBMIT DETAILS
 ON THE TYPE OF CATHODIC PROTECTION, SIZE (LBS.) & A
 NUMBER OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE
 AND AMOUNT OF WATER TO ACTIVATE IT.
 14. IF AN UNDERGROUND UNIT CLEARLY INDICATE ON TIE-DOWN
 SHEET IF THE LP TANK TIE-DOWN METHOD AND IF YOU ARE
 USING STRAPS OR CABLE, IF CABLE HOW IS IT PROTECTED FOR
 THE LP TANK AND APPURTENANCES PER NFPA 58. WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 15. PROVIDE THE SIZE OF THE HOLD-DOWN CABLES/STRAPS FOR
 THE TANK AND THE TYPE AND LENGTH OF GROUND ANCHORS TO
 BE INSTALLED TO PREVENT FLOTATION. NFPA 58 SEC.
 6.6.1.6.
 16. THE TANK SHALL BE A MIN OF 10' FROM ANY SOURCE OF
 IGNITION ACCORDING TO NFPA TABLE 6.3.4.3 SEPARATION
 DISTANCE BETWEEN CONTAINER PRESSURE RELIEF VALVE AND
 BUILDING OPENINGS.
 17. SHOW THE DISTANCE OF THE LP TANK FROM THE EXTERIOR
 WALL OF THE STRUCTURE TO THE CONTAINER SURFACE AND ALSO
 FROM THE PROPERTY LINE TO THE CONTAINER SURFACE. COMPLY
 WITH NFPA 58-11 SEC. 6.3.1 & TABLE 6.3.1.
 18. SHOW THE CAPACITY AND LOCATION OF THE LP TANK ON
 THE PLANS AND SHOW THE TYPE OF TANK (HORIZONTAL ASME OR
 VERTICAL ASME). WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  