Plan Review Notes For Permit 19090078
Permit Number 19090078
Review Stop G
Sequence Number 1
Notes
Date Text
2019-09-10 09:33:041) THE SUBMITTED GAS PLAN SHOWS AN EXISTING GAS
 TANKLESS WATER HEATER. CITY RECORDS DO NOT SHOW ANY
 EXISTING PERMIT FOR THIS INSTALLATION. IS THE
 INSTALLATION OF THIS TANKLESS WATER HEATER GOING TO BE
 INCLUDED IN THIS PERMIT. CLARIFY ON THE PLANS AND
 PERMIT APPLICATION. IF THE TANKLESS WATER HEATER WILL
 BE INCLUDED IN THIS PERMIT, SUBMIT TWO COPIES OF A
 HOUSE PLAN / FLOOR PLAN SHOWING THE LOCATION OF THE
 TANKLESS WATER HEATER AND THE LOCATION AND DISTANCE OF
 ANY OPERABLE DOORS OR WINDOWS IN RELATION TO THE
 TANKLESS WATER HEATER. THE LOCATION OF THE TANKLESS
 WATER HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN / FLOOR PLAN
 CAN BE HAND DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
 2) IF THE TANKLESS WATER HEATER IS BEING INCLUDED IN
 THIS PERMIT, SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE UNIT. WPB AMEND. TO FBC SEC.
 107.2.1.
 3) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS/INSTALLATION INSTRUCTIONS FOR THE
 PRESSURE REGULATOR BEING INSTALLED. WPB AMEND. TO FBC
 SEC. 107.2.1.
 4) A SHUTOFF VALVE SHALL BE LOCATED IMMEDIATELY
 UPSSTREAM OF THE REGULATOR. 2017 FBC-GAS SEC.409.4.
 5) WHERE CONNECTED TO RIGID PIPING, A UNION SHALL BE
 INSTALLED WITHIN ONE (1) FOOT OF EITHER SIDE OF THE MP
 REGULATOR. 2017 FBC-RESIDENTIAL SEC. G2421.2 (7), 2017
 FBC-FUEL GAS SEC. 410.2 (7).
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  