| 2019-10-21 10:49:02 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19090022 |
| | ADD: 2751 S. DIXIE HWY. |
| | CONT: RED DOOR CONSTRUCTION LLC |
| | TEL: 786-535-1006 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. OCT. 16/ 2019 |
| | ACTION: DENIED |
| | |
| | 1) WHEN VIEWING THE ADDRESS OF 2751 S DIXIE HWY THERE |
| | ARE 6 LOTS THAT APPEAR UNDER THIS ADDRESS AND ONE LARGE |
| | BUILDING? FIVE OF THE 6 LOTS HAVE LOT LINES THAT |
| | TRANSGRESS THROUGH THE BUILDING, EITHER THERE ARE FIRE |
| | WALLS WITH FIRE DOORS AT EACH PROPERTY LINE OR A UNITY |
| | OF TITLE IS REQUIRED. PLEASE PROVIDE ADDITIONAL |
| | INFORMATION ON THIS BUILDING. NOTE THIS EXERCISE MAY |
| | HAVE BEEN COMPLETED UNDER PREVIOUS PERMITS. WHEN THE |
| | CITY SUBMITS THE UNITY OF TITLE TO THE CLERK OF THE |
| | COURT AT THE COUNTY COMPLEX THEIR OFFICE (CLERK OF THE |
| | COURT) DOES NOT FORWARD THIS DOCUMENT TO THE PALM BEACH |
| | COUNTY PROPERTY APPRAISERS OFFICE SO THEY NEVER UPDATE |
| | THEIR RECORDS. |
| | |
| | UNITY OF TITLE. |
| | THE PROPOSED BUILDING STRUCTURE TRANSGRESSES LEGAL |
| | BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO FORM |
| | 'THE SITE'. A 'UNITY OF TITLE' SHALL BE RECORDED AT THE |
| | COUNTY COURTHOUSE. SUBMIT A COPY OF THE RECORDED 'UNITY |
| | OF TITLE' DOCUMENT SO THAT FBC TABLE 601 BOUNDARY LINE |
| | REQUIREMENTS MAY BE DEEMED NOT APPLICABLE. SEE WEBSITE |
| | FOR APPLICATION: |
| | HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP |
| | "APPLICATION FOR UNITY OF TITLE" |
| | HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45 |
| | -38-UNITYOFTITLE3.PDF |
| | VINCENT J NOEL |
| | SURVEYOR/REAL ESTATE SUPERVISOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH, FL 33401 |
| | PHONE: 494-1040 EXT: 1096 |
| | FAX: 494-1116 |
| | E-MAIL: [email protected] |
| | ********************************************* |
| | MANUEL JULIAN GONZALEZ |
| | ENGINEERING PROJECT COORDINATOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET, 4TH FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| | MAIN PHONE: (561) 822-1200 |
| | DIRECT: (561) 494-1085 |
| | FAX: (561) 494-1116 |
| | MOBILE: (561) 644-7301 |
| | EMAIL: [email protected] |
| | WWW.WPB.ORG/ENGINEERING |
| | |
| | 2) WE THANK YOU FOR THE NARRATIVE AS TO THE WORK TO BE |
| | PERFORMED UNDER THIS PERMIT BUT THERE ARE TWO CONCERNS |
| | THAT WE HAVE. |
| | 2A)(1) ON THE 1ST FLOOR LIFE SAFETY PLAN ONLY ONE STAIR |
| | IS SHOWN STAIR # 1. ON THE 2ND FLOOR LIFE SAFETY PLAN |
| | THE 2ND STAIRWAY IS SHOWN. THE PLANS (1ST FLOOR LIFE |
| | SAFETY PLAN) DOES SHOW COMPLIANCE WITH SECTION 1028.1 |
| | EXCEPTION 1.1 WHERE NOT MORE THAN 50% OF THE NUMBER OF |
| | REQUIRED EXITS CAN TRAVEL THROUGH A FREE AND |
| | UNOBSTRUCTED PATH OF TRAVEL TO AN EXTERIOR EXIT DOOR |
| | AND SUCH DOOR IS READILY VISIBLE AND IDENTIFIABLE FROM |
| | THE POINT OF TERMINATION OF THE ENCLOSURE. |
| | |
| | THE 2ND FLOOR LIFE SAFETY PLAN DOES SHOW THE LOCATION |
| | OF STAIRWELL # 2. NEITHER STAIRWELL INDICATES THEY ARE |
| | FIRE RATED AND WHAT HOUR THE SHAFTS ARE RATED. IT WOULD |
| | APPEAR ON THE 2ND FLOOR PLAN BOTH STAIRWAYS ARE |
| | INTERIOR EXIT STAIRWAYS. BOTH HAVE TO BE CONSTRUCTED IN |
| | ACCORDANCE WITH 1023.2 OF THE 2017 FBC-B FOR 2 HOURS IN |
| | A FOUR STORY BUILDING. |
| | |
| | 2A)(2) ON THE 1ST FLOOR STAIRWELL # TWO?S LOCATION IS |
| | NOT DECLARED ON THE PLAN, BUT COMPLIANCE WITH FBC.B |
| | 1023.1 NEEDS TO BE SHOWN. SECTION 1023.1 OF THE 2017 |
| | FBC-B DOES ALLOW FOR AN EXIT PASSAGEWAY CONSTRUCTED IN |
| | ACCORDANCE WITH SECTION 1024 OF THE 2017 FBC-B. PLEASE |
| | SHOW HOW COMPLIANCE WILL BE ACHIEVED. |
| | |
| | 2B) THE 2ND FLOOR LIFE SAFETY PLAN IN CORRIDOR # 210 |
| | HAS A NOTE THAT THE 2ND FLOOR OF BUILDING 1 A 4 STORY |
| | OFFICE MEETS EGRESS REQUIREMENTS AFTER THE DEMO OF |
| | BRIDGE BUILDING? IS THIS PART OF THIS PERMIT OR IS THIS |
| | WORK UNDER A SEPARATE PERMIT? 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 OF |
| | THE ADMINISTRATIVE CODE SECTION 107.2.1.2 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 3A) THE 1ST FLOOR LIFE SAFETY PLAN SHOWS 2 LOUNGES AN |
| | ACTIVE LOUNGE # 147 OF 912 SQUARE FEET AND A PASSIVE |
| | LOUNGE # 149 WITH 1925 SQUARE FEET. THE ACTIVE LOUNGE |
| | IS SHOWN AS A BUSINESS USE WHEREAS THE PASSIVE LOUNGE |
| | IS BEING SHOWN AS AN ASSEMBLY USE. IT WOULD APPEAR THAT |
| | BOTH LOUNGES ARE AN ASSEMBLY OCCUPANCY. IT WOULD APPEAR |
| | THIS IS A MIXED USE 1ST FLOOR WITH BUSINESS AND |
| | ASSEMBLY OCCUPANCIES RATHER THAN ACCESSORY OCCUPANCIES, |
| | SEE SECTION 508.2.3 OF THE 2017 FBC-B. WHEN THE PASSIVE |
| | AND ACTIVE SQUARE FOOTAGE ARE COMBINED THEY ADD UP TO |
| | 2837 SQ. FEET OR OVER 10 % OF THE 1ST FLOOR AREA. |
| | |
| | 3B) THE DESIGNER OF RECORD WILL NEED TO PROVIDE DESIGN |
| | CRITERIA FOR EITHER NON-SEPARATED OCCUPANCIES UNDER |
| | 508.3 OR 508.4 SEPARATION OF OCCUPANCIES IN COMPLIANCE |
| | WITH 508.2.4. |
| | |
| | 3C) THE OCCUPANCY COUNT WOULD NEED TO BE REVISED FOR |
| | THE ACTIVE LOUNGE TO 15 SQ. FT. PER OCCUPANT, SEE 2017 |
| | FBC-B TABLE 1004.1.2. |
| | |
| | 4) THE 1ST FLOOR LIFE SAFETY PLAN SHOWS THE ROOM USAGE |
| | FOR THE ACTIVE LOUNGE ROOM 147 AND 912 SQ. FT. BUT THE |
| | ROOM IDENTIFICATION TAG IS NOT OVER THE LOUNGE. THERE |
| | IS NO ROOM IDENTIFICATION TAG FOR THE AREA IN FRONT OF |
| | THE ROOM, LEASABLE SPACE 143 UNLESS THE SQ. FOOTAGE FOR |
| | THE LEASABLE SPACE IS INCLUDES THE ROOM NOT IDENTIFIED? |
| | ADDITIONAL INFORMATION IS REQUIRED. 107.2.1.2. |
| | |
| | 5A) BOTH THE 2ND FLOOR LIFE SAFETY PLAN AND THE LEVEL 2 |
| | FLOOR PLAN SHOW A 2 STORY ATRIUM. THE 2ND LEVEL FLOOR |
| | PLAN NOTE 33 INDICATES TO REPAIR EXISTING LOW WALL AND |
| | WINDOW FRAME. THE PLANS DO NOT HAVE A SECTION THROUGH |
| | THIS AREA NOR HOW COMPLIANCE WITH 404.6 ENCLOSURES OF |
| | ATRIUMS OF THE 2017 FBC-B IS TO BE COMPLIED WITH. SEE |
| | 404.6 AND EXCEPTIONS. |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 5B) DOES THE EXISTING CONFERENCE ROOM ##211 AND THE |
| | FUTURE TENANT SPACE 260 SHARED ATRIUM WALLS ALSO COMPLY |
| | WITH SECTION 404.6 AND OR EXCEPTIONS. |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 6) DISCREPANCY IN PLANS BOTH B102 LEVEL 2 LIFE SAFETY |
| | PLAN AND A-102 BOTH SHOW CLOSETS 203A & 203B. SHEET |
| | A-102 LEVEL 2 FLOOR PLAN INDICATES A DETAIL 1/ SHEET |
| | A-400. IT WOULD APPEAR THE WRONG DETAIL WAS PLACED |
| | UNDER THIS DETAIL. THERE IS 2 RESTROOMS PLUS AN |
| | ELEVATOR, RESTROOM CONFIGURATION DOES NOT MATCH THAT OF |
| | THE FLOOR PLAN AND 2ND FLOOR LIFE SAFETY PLAN. |
| | 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED, |
| | DISCREPANCY IN PLANS. |
| | |
| | 7) THE 2ND FLOOR LIFE SAFETY PLAN OCCUPANCY COUNT LEVEL |
| | 2 FOR ROOM 260 THE FUTURE TENANT SPACE 260 INDICATES A |
| | SQ. FOOTAGE OF 3732 SQ. FT. AND AN OCCUPANT LOAD OF 37, |
| | YOU ALWAYS ROUND UP TO THE NEXT WHOLE NUMBER YOU DO NOT |
| | DROP PART OF AN OCCUPANT, YOU ALWAYS ROUND UP TO THE |
| | NEXT WHOLE NUMBER. BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA INFORMAL INTERPRETATION. |
| | |
| | 8) SHEET A-102 THE 2ND LEVEL FLOOR PLAN, PLAN NOTE A05 |
| | INDICATES ALIGN NEW WINDOWS BELOW EXISTING LEVEL 3 |
| | WINDOWS. NEW WINDOWS SHALL MATCH EXISTING BUTT GLAZED |
| | PANEL WIDTH DIRECTLY ABOVE LEVEL 3. REFER TO SHEET |
| | A-803. NO SUCH SHEET WAS UPLOADED IN THIS REVIEW. THE |
| | PLANS GO FROM A-800 TO A-810. ADDITIONAL INFORMATION IS |
| | REQUIRED. 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE |
| | 107.2.1.2. |
| | |
| | 8A) SHEET A-102 THE 2ND LEVEL FLOOR PLAN, PLAN NOTE A05 |
| | INDICATES ALIGN NEW WINDOWS BELOW EXISTING LEVEL 3 |
| | WINDOWS. NEW WINDOWS SHALL MATCH EXISTING BUTT GLAZED |
| | PANEL WIDTH DIRECTLY ABOVE THE LEVEL 3. PLEASE NOTE IN |
| | THIS REVIEW NO PRODUCT APPROVALS WERE SUBMITTED FOR THE |
| | NEW WINDOWS. |
| | 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS |
| | |
| | 8B) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 |
| | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| | LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 8C) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 8D) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 9) THIS REVIEW SHEET A102 NOTE 5 INDICATED NEW WINDOWS. |
| | THERE WAS NO WIND DESIGN CRITERIA SUBMITTED IN THIS |
| | REVIEW. |
| | 2017 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 9.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| | DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| | |
| | 9.2. RISK CATEGORY. |
| | |
| | 9.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. |
| | |
| | 9.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 9.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. |
| | 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | |
| | 10) SHEET A-600 PLATFORM AND RAISED SEATING DETAIL. |
| | PLEASE INDICATE WHERE THE RAISED PLATFORM AND SEATING |
| | IS TO OCCUR. I COULD NOT FIND A SECTION ON THE LIFE |
| | SAFETY FOR THE 1ST AND 2ND FLOOR PLANS NOR THE |
| | ARCHITECTURAL PLAN WHERE THIS OCCURS. THE CODE ANALYSIS |
| | SHEET INDICATES THIS BUILDING IS CONSTRUCTION TYPE |
| | II-B. |
| | |
| | 10A) THIS SHEET DOES NOT PROVIDE ANY DESIGN CRITERIA |
| | FOR THE DESIGN OF THE PLATFORM. PLEASE REVIEW THE 2017 |
| | FBC-B TABLE 1607.1(4) & (FOOTNOTE M) FOR MINIMUM LIVE |
| | LOAD REQUIREMENTS. |
| | |
| | 10B) THE DETAILS INDICATE THE USE OF METAL STUD |
| | FRAMING. THE PLANS ARE SILENT AS TO THE GAUGE TO BE |
| | INSTALLED FOR STRUCTURAL STUDS. 2017 FBC-B SECTIONS |
| | 2211.1 & 2211.5 FLOOR SYSTEM DESIGN. |
| | |
| | 10C) THE PLAN IS SILENT AS TO THE HEIGHT OF THE |
| | PLATFORM. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 10D) PLEASE NOTE THIS SHEET INDICATES THE SUBSTRATE |
| | FLOOR SHEATHING IS TO BE 2 LAYERS OF ? INCH PLYWOOD. |
| | PLEASE REVIEW THE 2017 FBC-B SECTION 410.4 PLATFORM |
| | CONSTRUCTION AND AREA A PLATFORM CAN OCCUPY, 1/3RD THE |
| | MAIN FLOOR AREA. WILL THERE BE STORAGE UNDER THE |
| | PLATFORM? |
| | |
| | 11) , ASBESTOS COMMERCIAL: PLEASE PROVIDE A SIGNED |
| | ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD, |
| | STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF |
| | ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF |
| | HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT |
| | NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL |
| | INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE |
| | FOUND ON THEIR WEBSITE: |
| | |
| | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE |
| | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/_DOCUMENTS/ASBESTOS- |
| | NOTIFICATION-FORM-PBC-FILLABLE-UPDATE-07-30-2015.PDF |
| | |
| | 12) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |