| 2019-12-11 06:13:58 | 1) SHT. A0.02 - EXHIBIT "A" - NOTE #6 - REFERS TO A |
| | MINIMUM 1500 GALLON GREASE INTERCEPTOR TO BE INSTALLED |
| | YET SHT. P.01 AND CIVIL DRAWING WS.2 ( SHT. 3 OF 13 ) |
| | SHOW A 1250 GALLON INTERCEPTOR. ALSO, SEE NOTE #6 UNDER |
| | EXHIBIT "B' WHICH REFERS TO A 1000 GALLON MINIMUM |
| | CAPACITY GREASE INTERCEPTOR.CLARIFY. |
| | 2) SHT. P.01 SHOWS THE ORIENTATION OF THE GREASE |
| | INTERCEPTOR PERPENDICULAR TO THE BUILDING AND SHT. WS.2 |
| | SHOWS THE INTERCEPTOR ORIENTATION PARALLEL TO THE |
| | BUILDING. CLARIFY. |
| | 3) SHT. A0.02 - EXHIBIT "A" - NOTE #4 - REFERS TO A 1.5 |
| | INCH OR GREATER DOMESTIC WATER SUPPLY LINE AND EXHIBIT |
| | "B" REFERS TO A 2 INCH OR GREATER DOMESTIC WATER SUPPLY |
| | LINE.CLARIFY. |
| | 4) SHT. A2.02 - SUBMIT A STORM WATER RISER FOR THE ROOF |
| | DRAINAGE SYSTEM. THE SIZE OF VERTICAL AND HORIZONTAL |
| | DRAIN SIZING SHALL COMPLY WITH 2017 FBC-PLUMBING |
| | SEC.1106.2, 1106.3. IN SIZING ROOF DRAINS AND STORM |
| | DRAINAGE PIPING, ONE-HALF OF THE AREA OF ANY VERTICAL |
| | WALL THAT DIVERTS RAINWATER TO THE ROOF SHALL BE ADDED |
| | TO THE PROJECTED ROOF AREA FOR INCLUSION IN SIZING THE |
| | STORM DRAINAGE SYSTEM.2017 FBC-PLUMBING SEC.1106.4, WPB |
| | AMEND. TO FBC SEC.107.3.5.1.3. |
| | 5) SHT.P0.1 - THE PLANS REFERENCE TWO DIFFERENT GAS |
| | SIZING TABLES IN THE FLORIDA GAS CODE. THESE TABLES ARE |
| | FOR GALVANIZED PIPE. WHAT TYPE OF PIPE IS BEING |
| | INSTALLED UNDERGROUND AND WHAT SIZING TABLE IS BEING |
| | USED? GALVANIZED PIPE IS NOT PERMITTED UNDERGROUND. |
| | 2017 FGC SEC.404.11. |
| | 6) A SEPARATE PERMIT WILL BE REQUIRED FOR THE |
| | INSTALLATION OF THE PROPANE TANK AND GAS PIPING. PLACE |
| | A NOTE TO THIS EFFECT ON SHT. P0.1.WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | 7) A SEPARATE PERMIT WILL BE REQUIRED FOR THE |
| | INSTALLATION OF THE GREASE INTERCEPTOR. PLACE A NOTE TO |
| | THIS EFFECT ON SHT. P.01.WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 8) A SEPARATE PERMIT WILL BE REQUIRED FOR THE |
| | INSTALLATION OF THE BACKFLOW PREVENTER(S). TWO COPIES |
| | OF MANUFACTURER SPECIFICATIONS FOR THE DEVICE(S) SHALL |
| | BE SUBMITTED AT TIME OF PERMIT SUBMITTAL. ALL BACKFLOW |
| | DEVICES SHALL BE LEAD FREE PER CITY OF WEST PALM BEACH |
| | CROSS CONNECTION CONTROL MANUAL. PLACE A NOTE TO THIS |
| | EFFECT ON SHT. P.01. |
| | |
| | NOTE: THERE ARE ADDITIONAL GAS PLAN REVIEW COMMENTS |
| | UNDER THE GAS REVIEW STOP. |
| | |