Plan Review Notes
Plan Review Notes For Permit 19081537
Permit Number 19081537
Review Stop P
Sequence Number 2
Notes
Date Text
2019-12-11 06:13:581) SHT. A0.02 - EXHIBIT "A" - NOTE #6 - REFERS TO A
 MINIMUM 1500 GALLON GREASE INTERCEPTOR TO BE INSTALLED
 YET SHT. P.01 AND CIVIL DRAWING WS.2 ( SHT. 3 OF 13 )
 SHOW A 1250 GALLON INTERCEPTOR. ALSO, SEE NOTE #6 UNDER
 EXHIBIT "B' WHICH REFERS TO A 1000 GALLON MINIMUM
 CAPACITY GREASE INTERCEPTOR.CLARIFY.
 2) SHT. P.01 SHOWS THE ORIENTATION OF THE GREASE
 INTERCEPTOR PERPENDICULAR TO THE BUILDING AND SHT. WS.2
 SHOWS THE INTERCEPTOR ORIENTATION PARALLEL TO THE
 BUILDING. CLARIFY.
 3) SHT. A0.02 - EXHIBIT "A" - NOTE #4 - REFERS TO A 1.5
 INCH OR GREATER DOMESTIC WATER SUPPLY LINE AND EXHIBIT
 "B" REFERS TO A 2 INCH OR GREATER DOMESTIC WATER SUPPLY
 LINE.CLARIFY.
 4) SHT. A2.02 - SUBMIT A STORM WATER RISER FOR THE ROOF
 DRAINAGE SYSTEM. THE SIZE OF VERTICAL AND HORIZONTAL
 DRAIN SIZING SHALL COMPLY WITH 2017 FBC-PLUMBING
 SEC.1106.2, 1106.3. IN SIZING ROOF DRAINS AND STORM
 DRAINAGE PIPING, ONE-HALF OF THE AREA OF ANY VERTICAL
 WALL THAT DIVERTS RAINWATER TO THE ROOF SHALL BE ADDED
 TO THE PROJECTED ROOF AREA FOR INCLUSION IN SIZING THE
 STORM DRAINAGE SYSTEM.2017 FBC-PLUMBING SEC.1106.4, WPB
 AMEND. TO FBC SEC.107.3.5.1.3.
 5) SHT.P0.1 - THE PLANS REFERENCE TWO DIFFERENT GAS
 SIZING TABLES IN THE FLORIDA GAS CODE. THESE TABLES ARE
 FOR GALVANIZED PIPE. WHAT TYPE OF PIPE IS BEING
 INSTALLED UNDERGROUND AND WHAT SIZING TABLE IS BEING
 USED? GALVANIZED PIPE IS NOT PERMITTED UNDERGROUND.
 2017 FGC SEC.404.11.
 6) A SEPARATE PERMIT WILL BE REQUIRED FOR THE
 INSTALLATION OF THE PROPANE TANK AND GAS PIPING. PLACE
 A NOTE TO THIS EFFECT ON SHT. P0.1.WPB AMEND. TO FBC
 SEC. 107.2.1.
 7) A SEPARATE PERMIT WILL BE REQUIRED FOR THE
 INSTALLATION OF THE GREASE INTERCEPTOR. PLACE A NOTE TO
 THIS EFFECT ON SHT. P.01.WPB AMEND. TO FBC SEC.
 107.2.1.
 8) A SEPARATE PERMIT WILL BE REQUIRED FOR THE
 INSTALLATION OF THE BACKFLOW PREVENTER(S). TWO COPIES
 OF MANUFACTURER SPECIFICATIONS FOR THE DEVICE(S) SHALL
 BE SUBMITTED AT TIME OF PERMIT SUBMITTAL. ALL BACKFLOW
 DEVICES SHALL BE LEAD FREE PER CITY OF WEST PALM BEACH
 CROSS CONNECTION CONTROL MANUAL. PLACE A NOTE TO THIS
 EFFECT ON SHT. P.01.
  
 NOTE: THERE ARE ADDITIONAL GAS PLAN REVIEW COMMENTS
 UNDER THE GAS REVIEW STOP.
  