2019-12-11 09:09:591) SHT.P0.1 - THE PLANS REFERENCE TWO DIFFERENT GAS
 SIZING TABLES IN THE FLORIDA GAS CODE. THESE TABLES ARE
 FOR GALVANIZED PIPE. WHAT TYPE OF PIPE IS BEING
 INSTALLED UNDERGROUND AND WHAT SIZING TABLE IS BEING
 USED? GALVANIZED PIPE IS NOT PERMITTED UNDERGROUND.
 2017 FGC SEC.404.11.
 2) SHOW THE TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT
 PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL
 SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND
 THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF
 VALVE OF THE TANK PER NFPA 58, TABLE 3-2.2.2.
 3) SHOW THE METHOD OF REQUIRED PROTECTION FOR THE LP
 TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS
 BELOW GROUND IT SHALL BE ANCHORED PER NFPA 58
 SEC.3-2.2.7 (H).
 4) ) SUBMIT MANUFACTURER?S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS.
 REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING
 SHALL BE APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON
 THE SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING
 INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR
 CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR.2017
 FGC SEC.410.1,
 5) PROVIDE THE SIZE OF THE HOLD-DOWN CABLES/STRAPS FOR
 THE TANK AND THE TYPE AND LENGTH OF GROUND ANCHORS TO
 BE INSTALLED TO PREVENT FLOTATION. NFPA 58 SEC.
 6.6.1.6.
 6) ) A CATHODIC PROTECTION SYSTEM SHALL BE REQUIRED PER
 NFPA 58 SECS. 5.2.1.11, 6.6.6.1 (I) AND SHALL BE
 MONITORED PER NFPA 58 SEC.6.6.6.1 (J). SUBMIT DETAILS
 ON THE TYPE OF CATHODIC PROTECTION, SIZE (LBS) & NUMBER
 OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE.
 7) ) INSTALLATIONS WITHIN 10 FT (3 M) OF A PUBLIC
 VEHICULAR THOROUGHFARE OR DESIGNATED PARKING LOCATION
 SHALL BE PROVIDED WITH VEHICULAR BARRIER PROTECTION FOR
 THE CONTAINER?S FITTING HOUSING, HOUSING COVER,
 CONTAINER CONNECTIONS, AND PIPING. NFPA 58-14 SEC.
 6.6.6.1 (C)
 8) NFPA 58 SEC.6.9.4.6 - AN ELECTRICALLY CONTINUOUS
 CORROSION-RESISTANT TRACER WIRE (MINIMUM AWG 14) OR
 TAPE SHALL BE BURIED WITH THE POLYAMIDE OR POLYETHYLENE
 PIPE TO FACILITATE LOCATING THE PIPE.
  
 NOTE - A COMPLETE AND THOROUGH REVIEW COULD NOT BE DONE
 AT THIS TIME DUE TO THE LACK OF REQUIRED INFORMATION ON
 THE PLANS / DRAWINGS AND ADDITIONAL PLAN REVIEW
 COMMENTS MAY BE GENERATED UPON THE RE-REVIEW OF
 SUBMITTED CORRECTIONS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  