| Date |
Text |
| 2019-12-11 09:09:59 | 1) SHT.P0.1 - THE PLANS REFERENCE TWO DIFFERENT GAS |
| | SIZING TABLES IN THE FLORIDA GAS CODE. THESE TABLES ARE |
| | FOR GALVANIZED PIPE. WHAT TYPE OF PIPE IS BEING |
| | INSTALLED UNDERGROUND AND WHAT SIZING TABLE IS BEING |
| | USED? GALVANIZED PIPE IS NOT PERMITTED UNDERGROUND. |
| | 2017 FGC SEC.404.11. |
| | 2) SHOW THE TYPE OF TANK (DOT OR ASME), THE DISTANCE OF |
| | THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT |
| | PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL |
| | SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND |
| | THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF |
| | VALVE OF THE TANK PER NFPA 58, TABLE 3-2.2.2. |
| | 3) SHOW THE METHOD OF REQUIRED PROTECTION FOR THE LP |
| | TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS |
| | BELOW GROUND IT SHALL BE ANCHORED PER NFPA 58 |
| | SEC.3-2.2.7 (H). |
| | 4) ) SUBMIT MANUFACTURER?S SPECIFICATIONS AND |
| | INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS. |
| | REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING |
| | SHALL BE APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON |
| | THE SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING |
| | INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR |
| | CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR.2017 |
| | FGC SEC.410.1, |
| | 5) PROVIDE THE SIZE OF THE HOLD-DOWN CABLES/STRAPS FOR |
| | THE TANK AND THE TYPE AND LENGTH OF GROUND ANCHORS TO |
| | BE INSTALLED TO PREVENT FLOTATION. NFPA 58 SEC. |
| | 6.6.1.6. |
| | 6) ) A CATHODIC PROTECTION SYSTEM SHALL BE REQUIRED PER |
| | NFPA 58 SECS. 5.2.1.11, 6.6.6.1 (I) AND SHALL BE |
| | MONITORED PER NFPA 58 SEC.6.6.6.1 (J). SUBMIT DETAILS |
| | ON THE TYPE OF CATHODIC PROTECTION, SIZE (LBS) & NUMBER |
| | OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE. |
| | 7) ) INSTALLATIONS WITHIN 10 FT (3 M) OF A PUBLIC |
| | VEHICULAR THOROUGHFARE OR DESIGNATED PARKING LOCATION |
| | SHALL BE PROVIDED WITH VEHICULAR BARRIER PROTECTION FOR |
| | THE CONTAINER?S FITTING HOUSING, HOUSING COVER, |
| | CONTAINER CONNECTIONS, AND PIPING. NFPA 58-14 SEC. |
| | 6.6.6.1 (C) |
| | 8) NFPA 58 SEC.6.9.4.6 - AN ELECTRICALLY CONTINUOUS |
| | CORROSION-RESISTANT TRACER WIRE (MINIMUM AWG 14) OR |
| | TAPE SHALL BE BURIED WITH THE POLYAMIDE OR POLYETHYLENE |
| | PIPE TO FACILITATE LOCATING THE PIPE. |
| | |
| | NOTE - A COMPLETE AND THOROUGH REVIEW COULD NOT BE DONE |
| | AT THIS TIME DUE TO THE LACK OF REQUIRED INFORMATION ON |
| | THE PLANS / DRAWINGS AND ADDITIONAL PLAN REVIEW |
| | COMMENTS MAY BE GENERATED UPON THE RE-REVIEW OF |
| | SUBMITTED CORRECTIONS. |
| | |