| 2019-09-12 15:20:23 | 1. A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE |
| | COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION |
| | SUBMITTED ON THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS |
| | MAY BE GENERATED DURING PLAN RESUBMISSION. |
| | 2. PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY |
| | TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, |
| | EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF |
| | TRAVEL ETC. |
| | 3. PER SECTION 18.2.3.4.1.1 (NFPA 1), FIRE DEPARTMENT |
| | ACCESS ROADS SHALL HAVE A SURFACE DESIGNED TO |
| | ACCOMMODATE FIRE APPARATUS WEIGHING AT LEAST 36 TONS. |
| | ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED WIDTH OF NOT |
| | LESS THAN 20 FEET AND AN UNOBSTRUCTED VERTICAL |
| | CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES. |
| | 4. PER SECTION 18.2.3.5.3 (NFPA 1), FIRE LANES SHALL BE |
| | MARKED WITH FREESTANDING SIGNS READING, ?FIRE LANE - NO |
| | PARKING BY ORDER OF THE FIRE DEPARTMENT.? SIGNS SHALL |
| | BE 12? X 18? WITH A WHITE BACKGROUND AND RED LETTERS |
| | AND SHALL BE A MAXIMUM OF SEVEN FEET IN HEIGHT TO THE |
| | BOTTOM OF THE SIGN. SIGNS SHALL BE WITHIN SIGHT OF THE |
| | TRAFFIC FLOW AND BE SPACED A MAXIMUM OF 60 FEET APART. |
| | 5. DEAD-END FIRE DEPARTMENT ACCESS ROADS IN EXCESS OF |
| | 150 FEET IN LENGTH SHALL BE PROVIDED WITH APPROVED |
| | PROVISIONS FOR THE FIRE APPARATUS TO TURN AROUND. |
| | 6. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY |
| | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING |
| | ALL CONSTRUCTION ACTIVITIES. |
| | |