| 2019-09-21 10:34:13 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | 1. PROVIDE RISER DIAGRAM OF EXISTING RESIDENTIAL |
| | SERVICE. NEC 220.16A1&2, 220.12, 220.14 |
| | FBC RE 3602.1, FBC RE 3602.2, FBC 107.2.1 |
| | 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS. NEC 220; FBC RE E3602.2 |
| | 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; WPB FBC |
| | 107.3.5; FBC RE E3706.2, E3902 |
| | 4. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC EC R404.1 |
| | 5. RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS SHALL |
| | HAVE GFCI/AFCI PROTECTION. PROVIDE CORRECTION. NEC |
| | 210.12, 210.8(A)(9); FBC RE E3902.9 |
| | 6. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED |
| | PER CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE |
| | EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC |
| | RE R314.3, R315.1; WPB FBC 107.2.1 |
| | 7. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 |
| | 8. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C |
| | EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12 |
| | 9. INTERIOR PANEL IN LAUNDRY ROOM HAS NO WORKING |
| | CLEARANCE AS PER NEC 110.26(A1)&(A2) |
| | 10. RECEPTACLE REQUIRED OUTSIDE AT BOTH FRONT AND REAR |
| | OF DWELLING. NEC 210.52E1 |
| | 11. PROVIDE GFCI PROTECTED OUTLET AND SWITCH CONTROLLED |
| | LIGHT FOR SERVICING EACH AHU LOCATED IN AN ATTIC. FBC |
| | MECHANICAL CODE M306.3.1 |
| | 12. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP |
| | CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN, IN |
| | BATHROOMS. PROVIDE CORRECTION. NEC 210.11(C)(3), |
| | 210.52(D); FBC RE E3703.4, E3901.6 |
| | 13. LIGHT REQUIRED AT EXTERNAL SIDE OF EACH DOOR TO |
| | DWELLING THAT PROVIDES GRADE LEVEL ACCESS. (FRONT DOOR) |
| | NEC 210.70(A)(2)(B) |
| | 14. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING |
| | REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE |
| | INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG |
| | THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET |
| | FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION. NEC |
| | 210.52; FBC RE E3901.2.1 |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |
| | |