| 2019-12-10 08:18:55 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19081491 |
| | ADD: 250 S AUSTRALIAN AVE. SUITE # 1504 |
| | CONT:ADVANCED COMMERCIAL INTERIORS, INC. |
| | TEL: 954-580-6658 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: TUES. DEC. 10TH/ 2019 |
| | ACTION: DENIED |
| | |
| | |
| | ***************4X FEE / NOTICE!!!!! FLORIDA STATUTE |
| | 553.80(2)(B) ***************** |
| | |
| | |
| | |
| | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | |
| | 1) 2ND REQUEST. SAME COMMENT. 2017 EXISTING BUILDING |
| | CODE. 801.3 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, |
| | COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| | REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING. |
| | PLEASE NOTE ON SHEET A1.1.1 PLEASE SHOW COMPLIANCE WITH |
| | THE 2017 FBC-ACCESSIBILITY CODE SECTION CODE 404.2.4 |
| | MANEUVERING CLEARANCES. DOORS. MINIMUM MANEUVERING |
| | CLEARANCES AT DOORS AND GATES SHALL COMPLY WITH |
| | 404.2.4. MANEUVERING CLEARANCES SHALL EXTEND THE FULL |
| | WIDTH OF THE DOORWAY AND THE REQUIRED LATCH SIDE FOR |
| | SIDE CLEARANCE AND FIGURE 404.2.4.1(A) 18 INCHES ON THE |
| | PULL SIDE OF THE DOOR LATCH SIDE FOR THE FOLLOWING |
| | DOORS: |
| | |
| | 1A) DOOR 1505 NO, DOES NOT SHOW COMPLIANCE WITH THE |
| | 2017 FBC-ACCESSIBILITY CODE 404.2.4.1(A) REQUIRING 18 |
| | INCHES ON THE PULL SIDE OF THE LATCH SIDE OF THE DOOR. |
| | |
| | 1B) DOOR 1513 NO, DOES NOT SHOW COMPLIANCE WITH THE |
| | 2017 FBC-ACCESSIBILITY CODE 404.2.4.1(A) REQUIRING 18 |
| | INCHES ON THE PULL SIDE OF THE LATCH SIDE OF THE DOOR. |
| | |
| | 1C) DOOR 1514 NO, DOES NOT SHOW COMPLIANCE WITH THE |
| | 2017 FBC-ACCESSIBILITY CODE 404.2.4.1(A) REQUIRING 18 |
| | INCHES ON THE PULL SIDE OF THE LATCH SIDE OF THE DOOR. |
| | |
| | |
| | 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |