Plan Review Notes
Plan Review Notes For Permit 19081491
Permit Number 19081491
Review Stop B
Sequence Number 2
Notes
Date Text
2019-12-10 08:18:552017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19081491
 ADD: 250 S AUSTRALIAN AVE. SUITE # 1504
 CONT:ADVANCED COMMERCIAL INTERIORS, INC.
 TEL: 954-580-6658
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. DEC. 10TH/ 2019
 ACTION: DENIED
  
  
 ***************4X FEE / NOTICE!!!!! FLORIDA STATUTE
 553.80(2)(B) *****************
  
  
  
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 1) 2ND REQUEST. SAME COMMENT. 2017 EXISTING BUILDING
 CODE. 801.3 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.
 PLEASE NOTE ON SHEET A1.1.1 PLEASE SHOW COMPLIANCE WITH
 THE 2017 FBC-ACCESSIBILITY CODE SECTION CODE 404.2.4
 MANEUVERING CLEARANCES. DOORS. MINIMUM MANEUVERING
 CLEARANCES AT DOORS AND GATES SHALL COMPLY WITH
 404.2.4. MANEUVERING CLEARANCES SHALL EXTEND THE FULL
 WIDTH OF THE DOORWAY AND THE REQUIRED LATCH SIDE FOR
 SIDE CLEARANCE AND FIGURE 404.2.4.1(A) 18 INCHES ON THE
 PULL SIDE OF THE DOOR LATCH SIDE FOR THE FOLLOWING
 DOORS:
  
 1A) DOOR 1505 NO, DOES NOT SHOW COMPLIANCE WITH THE
 2017 FBC-ACCESSIBILITY CODE 404.2.4.1(A) REQUIRING 18
 INCHES ON THE PULL SIDE OF THE LATCH SIDE OF THE DOOR.
  
 1B) DOOR 1513 NO, DOES NOT SHOW COMPLIANCE WITH THE
 2017 FBC-ACCESSIBILITY CODE 404.2.4.1(A) REQUIRING 18
 INCHES ON THE PULL SIDE OF THE LATCH SIDE OF THE DOOR.
  
 1C) DOOR 1514 NO, DOES NOT SHOW COMPLIANCE WITH THE
 2017 FBC-ACCESSIBILITY CODE 404.2.4.1(A) REQUIRING 18
 INCHES ON THE PULL SIDE OF THE LATCH SIDE OF THE DOOR.
  
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  