| 2019-09-30 07:23:57 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19081475 |
| | ADD: 1641 WORTHINGTON RD. SUITE: 200 |
| | CONT: ANDERSON-MOORE CONSTRUCTION CORP. |
| | TEL: 561-348-4805 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. SEPT. 30/ 2019 |
| | ACTION: DENIED |
| | |
| | 1) THE LIFE SAFETY PLAN AND SHEET A1.1 SHOWS THE |
| | OVERALL DIAGONAL DISTANCE OF SUITE # 200 BUT NOT THE |
| | 1/3RD THE DISTANCE BETWEEN THE EXIT DOORS. PLEASE |
| | PROVIDE THE DISTANCE BETWEEN THE MAIN ENTRY DOOR (200) |
| | AND DOOR # 213. |
| | PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B SECTION |
| | 1007.1.1EXCEPTION # 2. WHERE A BUILDING IS EQUIPPED |
| | THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE WITH 903.3.1.1. THE SEPARATION DISTANCE |
| | SHALL NOT BE LESS THAN 1/3 THE OVERALL DIAGONAL |
| | DIMENSION OF THE AREA SERVED. |
| | |
| | 2) THE PROPOSED NEWLY RECONFIGURED FORMED TENANT SPACE |
| | JUST BENEATH ROOM 214 ALSO IS MISSING THE OVERALL |
| | DIAGONAL DIMENSION AND THE DIAGONAL DISTANCE BETWEEN |
| | THE EXISTING EXIT ACCESS DOOR AND THE PROPOSED OPENING |
| | 213 A. |
| | PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B SECTION |
| | 1007.1.1EXCEPTION # 2. WHERE A BUILDING IS EQUIPPED |
| | THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE WITH 903.3.1.1. THE SEPARATION DISTANCE |
| | SHALL NOT BE LESS THAN 1/3 THE OVERALL DIAGONAL |
| | DIMENSION OF THE AREA SERVED. |
| | |
| | 3) DISCREPANCY IN THE PLANS SHEET A1.1 THE NEW PROPOSED |
| | FRONT ENTRY DOOR IS DESIGNATED WITH A DOOR TAG 200. |
| | SHEET A2.0 IN THE DOOR SCHEDULE DOOR # 200 THE DOOR IS |
| | IDENTIFIED AS A 1 ? INCH WOOD DOOR IDENTIFIED AS DOOR |
| | TYPE E. ON THE SAME SHEET IN THE DOOR ELEVATIONS IS |
| | WHERE THE DISCREPANCY OCCURS. THE WORDING BENEATH THE |
| | PICTURE INDICATES A 45 MINUTE RATED SOLID CORE WOOD |
| | DOOR BUT DEPICTED IS A GLAZED DOOR. |
| | DISCREPANCY, PLEASE PROVIDE ADDITIONAL INFORMATION |
| | 107.2.1.2. PLEASE REVIEW OPENING PROTECTIVES UNDER |
| | FBC-B TABLE 716.5 AND &16.6. |
| | |
| | 4) SHEET A2.0 DOORS IDENTIFIED AS DOOR TYPE A INDICATES |
| | THEY ARE TO BE RE-USED AND WITH A SIDE LITE. NEITHER |
| | THE DOOR SCHEDULE NOR DOOR ELEVATIONS INDICATE WHAT |
| | TYPE OF GLAZING IS IN THE SIDE-LITE. |
| | PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B FOR |
| | HAZARDOUS LOCATIONS, SECTION 2406.4.2 GLAZING ADJACENT |
| | TO DOORS. 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE |
| | 104.9.1 USED MATERIALS. THE USE OF USED, RECYCLED OR |
| | RECLAIMED MATERIALS WHICH MEETS THE REQUIREMENTS OF |
| | THIS CODE FOR NEW MATERIALS IS PERMITTED. |
| | |
| | 5) THE SAME QUESTION AS THE PLUMBING PLANS EXAMINER, |
| | THE DEMOLITION PLAN AD1.1 DOES NOT SHOW THE BREAK ROOM |
| | CABINETRY NOR SINK NOR IS THERE ANY NOTES UNDER THE |
| | HEADING OF DEMOLITION KEYNOTES OR PLUMBING DEMOLITION |
| | NOTES? ADDITIONAL INFORMATION IS REQUIRED 107.2.1.2 FOR |
| | COMPLIANCE WITH: |
| | |
| | 5A) 2017 FBC-ACCESSIBILITY CODE 606.2 CLEAR FLOOR |
| | SPACE. A CLEAR FLOOR SPACE COMPLYING WITH 305, |
| | POSITIONED FOR A FORWARD APPROACH, AND KNEE AND TOE |
| | CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED. |
| | EXCEPTIONS: |
| | 1.A PARALLEL APPROACH COMPLYING WITH 305 SHALL BE |
| | PERMITTED TO A KITCHEN SINK, IN A SPACE WHERE A COOK |
| | TOP OR CONVENTIONAL RANGE IS NOT PROVIDED, AND TO WET |
| | BARS. |
| | |
| | 5B) 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT. |
| | LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| | OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 5C) WORK SURFACES.2017 FBC-ACCESSIBILITY CODE 902.3 |
| | HEIGHT. THE TOPS OF WORK SURFACES SHALL BE 28 INCHES |
| | MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. |
| | |
| | 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |