2019-09-25 07:59:42FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE 3-14 SHOWS NO ELECTRIC IN SIGN AND DOES NOT SHOW
 THE LOCATION OF THE REQUIRED DISCONNECT PER 600.5(A)(1)
  
 NEED TO SHOW HOW THIS SIGN COST $894.00 WHEN THE BILL
 FROM SIGN MANUFACTURER SSTARTS WITH $7609.00
 PLEASE BREAK DOWN EACH SIGN AND COST OF SIGN AND
 INSTALLATION. $894.00 NOT REASONABLE FOR PERMITTING.