| Plan Review Notes For Permit 19081447 |
| Permit Number |
19081447 |
|
| Review Stop |
Z |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-04-25 12:35:29 | INSUFFICIENT SUBMITTAL: | | | 1. PLEASE PROVIDE A SURVEY, PREPARED BY A FLORIDA | | | LICENSED SURVEYOR, THAT SHOWS THE RIGHT-OF-WAY LINE, | | | THE SIDEWALK, AND ANY TREES WITHIN THE RIGHT-OF-WAY | | | ALONG THE ENTIRE FIBER CONDUIT PATH SO THAT STAFF CAN | | | VERIFY THAT THE BORE AND HANDHOLES ARE WITHIN THE | | | RIGHT-OF-WAY. ALSO PROVIDE REFERENCE POLE IN SURVEY TO | | | COMPARE HEIGHTS. IF WORK OCCURS OUTSIDE OF ROW PLEASE | | | PROVIDE ON SURVEY PROOF OF GENERAL UTILITY EASEMENTS. | | | | | | 2. PLEASE PROVIDE PROPOSED POLE ELEVATIONS WITHIN SITE | | | PLAN. | | | | | | 3. PLEASE PROVIDE BORE PROFILE AND DEPTHS FOR ALL | | | UNDERGROUND FIBER/ELECTRICAL LINES AS WELL AS POLE | | | CAISSON. | | | | | | 4. PLEASE CONFIRM MINIMUM OF 36IN. OF CLEARANCE FOR ADA | | | BETWEEN FACE OF POLE AND EDGE OF SIDEWALK. | | | | | | 5. POLE COLOR SHALL MATCH DOWNTOWN STANDARD: RAYCAP | | | INTEGRATED POLE ??? RAL 7022 (UMBRA GRAY) | | | | | | CHRIS KIMMERLY, AICP | | | URBAN DESIGN PLANNER | | | [email protected] 561-822-1426 | | | |
|