| 2019-09-11 17:45:37 | 09/11/2019 1ST GAS/LP/TANK REVIEW **DENIED** WITH |
| | COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. GAS RISER DIAGRAM REQUIRED WPB AMENDMENTS TO THE FBC |
| | SEC. 107.3.5.3 (12) RESIDENTIAL GAS. |
| | 2. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC RES. |
| | SECS. G2413.4.1, G2413.4.2. |
| | 3. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR |
| | EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 4. TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 5. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER 2017 FBC RES. SEC. G2413.2. |
| | 6. PLEASE SHOW SHUTOFF VALVES, UNIONS, DRIP LEGS, BTU'S |
| | AND REGULATORS ON ISOMETRIC PER THE 2017 FBC RES. SEC. |
| | G2420.4. |
| | 7. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1? OF |
| | EITHER SIDE PER THE 2017 FBC FG SEC 410.2. |
| | 8. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC |
| | RES. SEC. G2413.4.1. |
| | 9. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE |
| | DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| | OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR |
| | ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS |
| | SYSTEM PER THE 2017 FBC RES. SEC. G2413.3. |
| | 10. SUBMIT TWO COPIES OF THE FOR INSTALLATION |
| | CLEARANCES FROM THE TANKLESS INSTALLATION MANUAL. THE |
| | MANUAL REQUIRES A CLEARANCE OF EITHER 4 FEET OR 12 |
| | INCHES FROM ANY OPERABLE WINDOWS OR DOORS. SHOW THE |
| | LOCATION OF ALL OPERABLE WINDOWS AND DOORS ON THE PLAN |
| | AND THE DISTANCE OF THE TANKLESS WATER HEATER FROM |
| | EACH. WPB AMENDMENTS TO THE FBC SEC. 107.2.1. |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 11. IF THIS TANKLESS UNIT CALL FOR 10.5? WATER COLUMN |
| | AND THE SERVICE METER DISCHARGES IS A 12? WATER COLUMN |
| | REQUIRING A REGULATOR FOR THIS UNIT AS PER |
| | MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER?S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES. |
| | SEC. G2421.1. |
| | 12. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2017 |
| | FBC RES. SEC. G2413.2 AND G2404.3. |
| | 13. SUBMIT COMPLETE MANUFACTURER'S SPECIFICATIONS FOR |
| | THE GAS DRYER, STOVE AND TANKLESS. THE GAS DRYER SHALL |
| | BE LISTED AND LABELED PER THE 2017 FBC FG RES. SEC. |
| | G2404.3. THE MANUFACTURER'S SPECIFICATIONS SHALL NOTE |
| | THE CFM'S THAT ARE BEING EXHAUSTED BY THE DRYER. |
| | 14. TOTAL BTU?S OF ALL APPLIANCES NOT ON PLAN IN P.1B |
| | FOR THE GAS TOTAL LOAD PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 15. SHOW THE SIZE OF THE LOUVER(S) ON THE DRYER ON |
| | PLANS AND LOCATION PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | |