| Plan Review Notes For Permit 19081361 |
| Permit Number |
19081361 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-08-29 12:17:16 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THIS PERMIT HAS TWO SEPARATE DESCRIPTION; CHANGE OF | | | OCCUPANCY/ FIRE SSPRINKLER. | | | | | | THESE CANNOT BE UNDER THE SAME PERMIT. | | | | | | PLEASE SEPARATE AND RESUBMIT. | | | | | | | | | | | | 2) FOR CHANGE OF OCCUPANCY, PLEASE PROVIDE DETAILS OF | | | WHAT IS BEING PROVIDED IN THIS OCCUPANCY? | | | | | | WHAT OCCUPANCY CLASSIFICATION PER THE FLORIDA FIRE | | | PREVENTION CODE WILL IT BE REQUIRED TO COMPLY WITH? | | | | | | PROVIDE A LIFE SAFETY PLAN INCLUDING FLOOR PLAN | | | DETAILS/DIMENSIONS, DOOR SIZES, EXIT HARDWARE, SMOKE | | | DETECTOR LOCATIONS, ETC, | | | | | | PLEASE PROVIDE | | | | | | | | | | | | 3) IT APPEARS THAT A WELL IS PROPOSED FOR THE FIRE | | | SPRINKLER; PER NFPA 13D AS PROPOSED. | | | | | | THE PUMP FOR THE WELL IS ELECTRIC, HOW WILL THIS BE | | | POWERED IN THE EVENT OF POWER FAILURE? | | | | | | HOW DO YOU PROPOSE TO VERIFY AND CONFIRM THE WATER | | | FLOW? | | | | | | | | | 4) ANY UNDERGROUND FIRE LINE SHALL BE INSTALLED PER | | | NFPA 24 BY A LICENSED UNDERGROUND CONTRACTOR PER THE | | | STATE OF FLORIDA. | | | | | | PLEAE ENSURE COMPLIANCE. | | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|